Full load performance performance data – Trane CGWF User Manual

Page 16

Advertising
background image

CG-PRC012-EN

16

Table PD-1. 60 Hz CGWF performance data in English units

Evaporator

Entering Condenser Water Temperature (F)

Leaving Water

Unit

75

80

85

90

95

Temperature (F)

Size

Tons

kW

EER

Tons

kW

EER

Tons

kW

EER

Tons

kW

EER

Tons

kW

EER

20

19.2

13.8

16.7

19.0

14.5

15.7

18.6

15.4

14.6

18.1

16.1

13.5

17.7

17.1

12.4

25

23.8

17.2

16.5

23.2

18.1

15.4

22.7

19.1

14.3

22.1

20.1

13.2

21.6

21.2

12.2

40

30

28.3

20.7

16.4

27.6

21.7

15.3

27.0

22.9

14.1

26.3

24.1

13.1

25.6

25.4

12.1

40

38.0

27.3

16.8

37.2

28.7

15.6

36.5

30.2

14.5

35.5

31.8

13.4

34.6

33.6

12.4

50

47.0

34.1

16.6

46.0

35.8

15.4

44.9

37.7

14.3

43.8

39.7

13.2

42.7

41.0

12.2

60

57.7

42.1

16.4

56.4

44.2

15.3

55.0

46.5

14.2

53.7

49.0

13.1

52.3

51.7

12.1

20

20.0

13.9

17.3

19.8

14.6

16.3

19.3

15.4

15.1

18.9

16.2

14.0

18.4

17.1

12.9

25

24.7

17.3

17.1

24.2

18.2

15.9

23.6

19.2

14.8

23.0

20.2

13.7

22.4

21.3

12.6

42

30

29.4

20.8

17.0

28.7

21.8

15.8

28.0

23.0

14.7

27.3

24.2

13.6

26.6

25.5

12.5

40

39.5

27.4

17.3

38.7

28.8

16.1

37.8

30.3

15.0

36.9

32.0

13.9

36.0

33.8

12.8

50

48.9

34.2

17.2

47.8

36.0

16.0

46.7

37.9

14.8

45.6

39.9

13.7

44.4

42.1

12.7

60

59.9

42.3

17.0

58.5

44.4

15.8

57.2

46.7

14.7

55.7

49.2

13.6

54.3

51.9

12.6

20

20.8

13.9

17.3

20.5

14.7

16.8

19.9

15.4

15.5

19.6

16.3

14.5

19.1

17.2

12.9

25

25.7

17.4

17.7

25.1

18.3

16.5

24.5

19.1

15.4

23.9

20.3

14.2

23.3

21.4

13.1

44

30

30.6

20.8

17.6

29.9

21.9

16.4

29.2

22.9

15.3

28.4

24.3

14.0

27.7

25.6

13.0

40

41.1

27.5

17.9

40.2

28.9

16.7

39.4

30.3

15.6

38.4

32.1

14.4

37.4

33.9

13.3

50

50.8

34.4

17.7

49.7

35.1

16.5

48.6

37.8

15.4

47.4

40.1

14.2

46.2

42.3

13.1

60

62.1

42.5

17.6

60.7

44.6

16.3

59.4

46.8

15.2

57.9

49.4

14.1

56.4

52.1

13.0

20

21.5

14.0

18.5

21.3

14.7

17.4

20.9

15.5

16.2

20.4

16.3

15.0

19.9

17.3

13.8

25

26.6

17.4

18.3

26.1

18.3

17.1

25.5

19.3

15.8

24.9

20.3

14.7

24.2

21.5

13.5

46

30

31.7

20.9

18.2

31.0

22.0

16.9

30.3

23.1

15.7

29.5

24.4

14.5

28.7

25.7

13.4

40

42.6

27.6

18.5

41.7

29.0

17.3

40.8

30.6

16.0

39.9

32.3

14.8

38.9

34.1

13.7

50

52.8

34.5

18.4

51.6

36.3

17.1

50.4

38.2

15.9

49.2

40.2

14.7

48.0

42.4

13.6

60

64.4

42.6

18.1

63.0

44.8

16.9

61.5

47.1

15.7

60.0

49.6

14.5

58.5

52.3

13.4

20

22.4

14.0

19.1

22.1

14.8

18.0

21.6

15.6

16.7

21.1

16.4

15.5

20.6

17.3

14.3

25

27.6

17.5

19.0

27.0

18.4

17.6

26.4

19.4

16.4

25.8

20.4

15.2

25.2

21.6

14.0

48

30

32.9

21.0

18.8

32.2

22.1

17.5

31.4

23.2

16.2

30.7

24.5

15.0

29.9

25.8

13.9

40

44.2

27.8

19.1

43.3

29.2

17.8

42.4

30.7

16.6

41.4

32.4

15.3

40.4

34.2

14.2

50

54.7

34.6

19.0

53.6

35.4

17.7

52.3

38.3

16.4

51.1

40.4

15.2

49.8

42.6

14.0

60

66.7

42.8

18.7

65.2

45.0

17.4

63.7

47.3

16.2

62.2

49.8

15.0

60.7

52.5

13.9

20

23.2

14.1

19.7

22.9

14.8

18.6

22.4

15.6

17.2

21.9

16.5

16.0

21.4

17.4

14.8

25

28.7

17.6

19.6

28.0

18.5

18.2

27.4

19.4

16.9

26.8

20.5

15.7

26.1

21.6

14.5

50

30

34.1

21.1

19.5

33.4

22.1

18.1

32.6

23.3

16.8

31.8

24.6

15.6

31.0

25.0

14.4

40

45.9

27.9

19.8

44.9

29.3

18.4

43.9

30.8

17.1

42.9

32.5

15.8

41.9

34.3

14.6

50

56.8

34.8

19.6

55.5

36.5

18.2

54.3

38.5

16.9

53.0

40.5

15.7

51.7

42.8

14.5

60

69.1

43.0

19.3

67.6

45.1

18.0

66.0

47.5

16.7

64.5

50.0

15.5

62.9

52.8

14.3

Notes:
1. Rated in accordance with ARI Standard 550/590-98 with fouling factors of 0.0001 in the evaporator and 0.00025 in the condenser.
2. Consult Trane representative for performance at temperatures outside of the ranges shown.
3. kW input is for compressors only.
4. EER = Energy Efficiency Ratio (Btu/watt-hout). Power inputs include compressors and control power.
5. Ratings are based on an evaporator temperature drop of 10°F.
6. Interpolation between points is permissible. Extrapolation is not permitted.

Full Load
Performance

Performance
Data

Advertising