Full load performance performance data – Trane CGWF User Manual

Page 22

Advertising
background image

CG-PRC012-EN

22

Table PD-9. 60 Hz CCAF performance data in Metric units

Evaporator

Entering Condenser Air Temperature (C)

Leaving Water

Unit

Condenser

30

35

40

45

Temperature (C)

Size

Size

kWo

kWi

COP

kWo

kWi

COP

kWo

kWi

COP

kWo

kWi

COP

20

CAUC-C20

69.4

19.8

3.5

66.2

21.7

3.0

62.5

23.8

2.6

58.7

26.2

2.2

20

CAUC-C25

70.7

18.9

3.7

67.3

20.7

3.2

63.8

22.9

2.8

60.3

25.1

2.4

25

CAUC-C25

86.2

25.3

3.4

82.1

27.8

2.9

77.8

30.5

2.5

73.1

33.5

2.2

25

CAUC-C30

87.8

23.8

3.7

84.0

26.2

3.2

79.7

28.8

2.8

75.2

31.7

2.4

6

30

CAUC-C30

103.0

29.6

3.5

98.2

32.4

3.0

93.1

35.6

2.6

87.9

39.1

2.2

30

CAUC-C40

104.7

27.4

3.8

100.3

30.1

3.3

95.3

33.1

2.9

90.2

36.4

2.5

40

CAUC-C40

138.4

39.5

3.5

131.9

43.3

3.0

124.8

47.6

2.6

117.5

52.4

2.2

40

CAUC-C50

140.0

38.1

3.7

133.6

41.9

3.2

126.8

46.0

2.7

119.5

50.7

2.3

50

CAUC-C50

170.2

51.0

3.3

162.3

56.0

2.9

153.8

61.5

2.5

144.8

67.5

2.1

50

CAUC-C60

173.5

47.8

3.6

165.7

52.5

3.1

157.6

57.9

2.7

149.0

63.7

2.3

60

CAUC-C60

203.5

59.2

3.4

194.1

65.2

3.0

184.2

71.6

2.6

173.6

78.7

2.2

60

CAUC-C80

206.0

54.5

3.8

197.0

59.9

3.3

187.6

66.1

2.8

177.5

72.7

2.4

20

CAUC-C20

73.5

20.2

3.6

70.0

22.1

3.1

66.2

24.3

2.7

62.3

26.7

2.3

20

CAUC-C25

74.8

19.2

3.9

71.5

21.1

3.4

67.7

23.3

2.9

63.9

25.5

2.5

25

CAUC-C25

91.3

25.8

3.5

86.8

28.3

3.1

82.4

31.0

2.6

77.6

34.1

2.3

25

CAUC-C30

93.3

24.3

3.8

89.1

26.6

3.3

84.6

29.3

2.9

79.9

32.1

2.5

8

30

CAUC-C30

109.1

30.2

3.6

104.0

33.0

3.1

98.9

36.2

2.7

93.2

39.8

2.3

30

CAUC-C40

111.1

27.8

4.0

106.3

30.5

3.5

101.4

33.6

3.0

96.1

36.9

2.6

40

CAUC-C40

146.1

39.5

3.7

139.3

44.0

3.1

132.2

48.5

2.7

124.6

53.2

2.3

40

CAUC-C50

148.0

38.6

3.8

141.3

42.4

3.3

134.3

46.7

2.9

126.9

51.4

2.5

50

CAUC-C50

179.9

52.0

3.4

171.5

56.9

3.0

162.8

62.5

2.6

153.3

68.7

2.2

50

CAUC-C60

183.7

48.5

3.8

175.6

53.4

3.3

167.0

58.7

2.8

158.0

64.6

2.4

60

CAUC-C60

215.1

60.4

3.5

205.4

66.3

3.1

195.1

72.8

2.7

184.3

80.0

2.3

60

CAUC-C80

217.9

55.3

3.9

208.6

61.0

3.4

198.6

67.0

3.0

188.4

73.8

2.5

20

CAUC-C20

77.4

20.6

3.7

73.8

22.6

3.3

70.0

24.7

2.8

65.9

27.1

2.4

20

CAUC-C25

78.9

19.6

4.0

75.4

21.5

3.5

71.9

23.6

3.0

67.8

25.9

2.6

25

CAUC-C25

96.4

26.2

3.7

92.0

28.8

3.2

87.2

31.6

2.7

82.4

34.6

2.4

25

CAUC-C30

98.7

24.6

4.0

94.2

27.0

3.5

89.7

29.7

3.0

84.7

32.5

2.6

10

30

CAUC-C30

115.2

30.7

3.7

110.1

33.7

3.3

104.6

36.9

2.8

98.9

40.4

2.4

30

CAUC-C40

117.5

28.3

4.1

112.7

31.0

3.6

107.3

34.0

3.1

101.8

37.4

2.7

40

CAUC-C40

154.0

40.9

3.7

147.0

44.9

3.3

139.6

49.2

2.8

131.7

54.1

2.4

40

CAUC-C50

156.0

39.3

3.9

149.3

43.1

3.4

142.0

47.4

3.0

134.0

52.1

2.6

50

CAUC-C50

189.7

52.9

3.6

181.1

57.9

3.1

171.8

63.5

2.7

162.3

69.8

2.3

50

CAUC-C60

193.9

49.3

3.9

185.6

54.1

3.4

176.6

59.6

3.0

167.1

65.4

2.5

60

CAUC-C60

227.2

61.6

3.7

216.9

67.6

3.2

206.4

74.1

2.8

195.0

81.4

2.4

60

CAUC-C80

230.4

56.1

4.1

220.8

61.6

3.6

210.2

67.9

3.1

199.4

74.7

2.7

Notes:
1. Ratings based on sea level altitude and evaporator fouling factor of 0.0176.
2. Consult Trane representative for performance at temperatures outside of the ranges shown.
3. kWi input is for compressors only.
4. COP = Coefficient of Performance (kWo/total kW). Total kW include compressors and control power.
5. Ratings are based on an evaporator temperature drop of 5.6°C.
6. Interpolation between points is permissible. Extrapolation is not permitted.
7. Rated in accordance with ARI Standard 550/590-98.