UPS 225 - 275 kVA

User’s and Installation Guide

1027212
Revision B

11

Dimensions are in millimeters.

Model

Weight kg

Shipping

Installed

Powerware 9395-275/225

930

830

Powerware 9395-275/275

930

830

Table 2-1. UPS cabinet weights

The UPS cabinets use forced air cooling to regulate internal component temperature. Air inlets
are in the front of the cabinet and outlets are in the top. You must allow clearance in front of and
above each cabinet for proper air circulation. The clearances required around the UPS cabinet
are shown in Table 2-2.

From top of cabinet

Minimum clearance over the UPS cabinet is 458 mm for ventilation

From front of cabinet

915 mm working space

From back of cabinet

None required

From right side of cabinet

None required, but for easier service 500 mm is recommended.

From left side of cabinet

None required

Table 2-2. UPS cabinet clearances

The basic environmental requirements for operation of the UPS system are:

Ambient Temperature Range: 0-40°C
Recommended Operating Range: 20-25°C
Maximum Relative Humidity: 95%, noncondensing

The UPS ventilation requirements are shown in Table 2-3.

Rating

Input/output voltage

Heat rejection

BTU/hr x 1000/hr (kg-cal/hr)

225 kVA

400/400

44.6 (10.1)

275 kVA

400/400

54.5 (13.7)

Table 2-3. Air conditioning or ventilation requirements during full load operation

Ventilation required for cooling air exhaust: approximately 1410 liter/sec.