10 product specifications, 1 model numbers, 2 single module specifications – Thomas & Betts 9395 User Manual

Page 73: 1 ups system input, 2 ups system output

Advertising
background image

UPS 225 - 275 kVA

User’s and Installation Guide

1027212
Revision B

73

10 Product specifications

10.1 Model numbers

The UPS systems are housed in free-standing cabinets with safety shields behind the doors. The
UPS systems are available in 50/60 Hz with various output power ratings.

Models

Power Rating

Frequency

Powerware 9395-275/225

225 kVA

50/60 Hz

Powerware 9395-275/275

275 kVA

50/60 Hz

The following sections detail the input, output, environmental, and battery specifications for the
UPS.

10.2 Single module specifications

10.2.1 UPS system input

Operating Input Voltage

(Nominal + –15%)

400 Vac for operation from 340 Vac to 460 Vac

Operating Input Frequency Range

±5 Hz

Operating Input Current

See Table 3-4 on page 3-6.

Reduced for Generator Adjustable

Input Current Harmonic Content

5% THD at full load

Power Factor

Minimum 0.98

Line Surges

6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801-4

Battery Voltage

480 Vdc

10.2.2 UPS system output

UPS Output Capacity

100% rated current

Output Voltage Regulation

±1% (10% to 100% load)

Output Voltage Adjustment (Nominal +/–3%)

380 Vac nominal, adjustable from 368.6 Vac to 391.4 Vac

400 Vac nominal, adjustable from 388 Vac to 412 Vac

415 Vac nominal, adjustable from 402.5 Vac to 427.5 Vac

Output Voltage Harmonic Content

1.5% max THD (linear load)

5% max THD (nonlinear load)

Output Current

See Table 3-4 on page 3-6.

Output Voltage Balance

3% for 100% maximum load imbalance (linear load)

Output Voltage Phase Displacement

3° for 100% maximum load imbalance (linear load)

Output Transients

±5% for 100% load step or removal

Frequency Regulation

±0.1 Hz free running

Synchronous to Bypass

Bypass within voltage limits of +5%, –8% of output setting;

bypass within ±3 Hz

Frequency Slew Rate

1 Hz per second maximum

Overload Capability

110% for 10 minutes

125% for 30 seconds

150% for 10 seconds