UPS 225 - 275 kVA

User’s and Installation Guide

1027212

Revision B

2

3.4.2 Battery wiring

CAUTION

When sizing the battery system, do not exceed the internal battery charger capabilities. See
Chapter 10, “Product specifications,” for maximum battery charger currents.

To install wiring to connections:

1. If using a Powerware battery cabinet, proceed to Step 2; otherwise, proceed to Step 5.

2. Route and connect the battery cables between the UPS and battery cabinets in accordance

with the instructions in the Powerware 9395 Integrated Battery Cabinet (Model IBC-L)
installation manual. See Figure 3-3 through Figure 3-5 for wiring access information and
terminal locations.

3. Connect the positive, negative, and ground DC power wiring from the battery cabinet to the

UPS cabinet battery and ground terminals. See paragraph 2.2.2 on page 14 for wiring and
termination requirements.

4. Proceed to Step 7.

5. Route and connect the battery cables between the UPS and the battery system. See Figure

3-3 through Figure 3-5 for wiring access information and terminal locations.

6. Connect the positive, negative, and ground DC power wiring from the battery system to the

UPS cabinet battery and ground terminals. See paragraph 2.2.2 on page 14 for wiring and
termination requirements.

7. After wiring the UPS system to the facility power and critical load, be sure to ground the

system according to local and/or national electrical wiring codes.

8. If wiring interface connections, proceed to paragraph 3.5; otherwise, proceed to Step 9.

9. When all wiring is complete, reinstall the left front panel removed in paragraph 3.4.1 and

secure with the retained hardware.

3.5 Installing interface connections

WARNING

Hazardous voltages are present near the user interface terminal area if the UPS is not
totally disconnected.

3.5.1 TB1, TB2, and TB3 connections (other than TB1 battery interface

connections)

NOTE

Interface wiring must be installed from the top of the UPS cabinet.