For reference – Toshiba CARRIER RAV-SP240AT2-UL User Manual

Page 12

Advertising
background image

Toshiba

– 11 –

Outdoor Unit

Installation Manual

3) Place unit on stand. Make sure it is level and

fasten securely to the stand.

• As shown in the figure below, install the

foundation and vibration-proof rubber pads to
directly support the bottom surface of the fixing
leg that is in contact with the bottom plate of the
outdoor unit.

• When installing the foundation for an outdoor

unit with downward piping, consider the piping
work.

• When water is to be drained through the drain hose,

attach the following drain nipple and waterproof
rubber cap, and use the drain hose (Inner diameter:
0.6” (16 mm)) sold on the market. Also seal the
screws securely with silicone material, etc., to
prevent water from leaking.
Some conditions may cause condensation or
dripping of water.

• When collectively draining discharged water

completely, use a drain pan.

„

For Reference

If a heating operation is to be continuously performed
for a long time under the condition that the outdoor
temperature is 32 °F (0 °C) or lower, draining defrosted
water may be difficult due to the bottom plate freezing,
resulting in trouble with the cabinet or fan.

GOOD

Mounting leg

Foundation

GOOD

NO GOOD

Foundation

Foundation

If only the end of the

mounting leg is

supported, it may

deform.

Do not support

the outdoor unit

only with the

mounting leg.

Bottom plate

of outdoor unit

Support the bottom surface of the

mounting leg that is in contact with

and underneath the bottom plate of

the outdoor unit.

Drain nipple

Waterproof rubber cap

(5pcs.)

Waterproof rubber cap

Drain nipple

11-EN

+00EH99865401_00Ta.book Page 11 Wednesday, November 25, 2009 11:19 AM

Advertising