Installation of new refrigerant air conditioner, Required tools/equipment and precautions for use – Toshiba CARRIER RAV-SP240AT2-UL User Manual

Page 8

Advertising
background image

Toshiba

– 7 –

Outdoor Unit

Installation Manual

5

INSTALLATION OF NEW REFRIGERANT

AIR CONDITIONER

CAUTION

New Refrigerant Air Conditioner Installation

THIS AIR CONDITIONER ADOPTS THE NEW HFC REFRIGERANT (R410A) WHICH DOES NOT DESTROY

OZONE LAYER.

R410A refrigerant is apt to be affected by impurities such as water, oxidizing membrane, and oils because the working
pressure of R410A refrigerant is approx. 1.6 times as that of refrigerant R22. Accompanied with the adoption of the new
refrigerant, the refrigerant oil has also been changed. Therefore, during installation work, be sure that water, dust,
former refrigerant, or refrigerant oil does not enter the new type refrigerant R410A air conditioner cycle.
To prevent mixing of refrigerant or refrigerant oil, the sizes of connecting sections of charging port on main unit and
installation tools are different from those of the conventional refrigerant units. Accordingly, special tools are required for
the new refrigerant (R410A) units. For connecting pipes, use new and clean piping materials with high pressure fittings
made for R410A only, so that water and/or dust does not enter.

„

Required Tools/Equipment and Precautions for Use

Prepare the tools and equipment listed in the following table before starting the installation work.

: R410A exclusive
: Generic

Tools/equipment

Use

Manifold gauge*

Vacuuming/charging refrigerant

and operation check

Charging hose
Gas leak detector

Gas leak check

Vacuum pump with backflow

prevention function

Vacuum drying

Flare tool

Flare machining of pipes

Usable if dimensions are adjusted.

Bender

Bending pipes

Refrigerant recovery equipment

Refrigerant recovery

Torque wrench

Tightening flare nuts

Ø1/2” (12.7 mm) and 5/8” (Ø15.9 mm)

Pipe cutter

Cutting pipes

Brazing torch and nitrogen

cylinder

Braze pipes

Refrigerant charging scales

Charging refrigerant

4 mm hexagon wrench

Opening liquid valve

7-EN

+00EH99865401_00Ta.book Page 7 Wednesday, November 25, 2009 11:19 AM