SYSTEM REQUIREMENTS

„

Piping (Field supplied)

• Minimum refrigerant line length between the outdoor

unit and indoor unit is 16.5” (5 m)

• Maximum pipe lengths

Figure of Single

Refrigerant sizes

Flare nuts and flaring

• The flare nuts and flaring are different from those for

the conventional refrigerant.
Use the flare nuts supplied with the air conditioner or
those for R410A.

• Before performing flaring, carefully read

“REFRIGERANT PIPING”

Insulation

Both lines need to be insulated. Use a minimum 0.4”
(10 mm) wall thickness.

Refrigerant charge

* Caution during addition of refrigerant

Max. amount of additional refrigerant is 1.8 lbs (800

g).

Charge the refrigerant accurately. Overcharging

may cause serious trouble with the compressor.

* Minimum refrigerant pipe is 16’5”(5 m).

This may cause a malfunction of the compressor or

other devices.

Metering Device is an electronic EXV (PMV) in

outdoor unit.

„

Connecting power and control
cables (Field supplied)

• The main power is supplied to the outdoor unit. The

field supplied connecting cables from the outdoor
unit to the indoor unit consist for 4 wires and provides
the power for the indoor unit as well as the
communication signal between the outdoor and
indoor unit.

• System interconnection wire size must be AWG12.
• Breaker must have a capacity specified in the

following table.

• All wiring must comply with local electric codes and

NEC (National Electric Code) or CEC (Canadian
Electric Code).

Allowable

pipe length

(ft (m))

Height difference

(Indoor-outdoor H)

(ft (m))

Number of

bent portions

Total length

L

Indoor unit:

Upper

Outdoor unit:

Lower

10 or less

164’1” (50)

98’5” (30)

98’5” (30)

Liquid side

Gas side

Outer

diameter

Thickness

Outer

diameter

Thickness

Ø3/8”

(9.5 mm)

0.03”

(0.8 mm)

Ø5/8”

(15.9 mm)

0.04”

(1.0 mm)

H

L

Indoor Unit

Outdoor Unit

Length of refrigerant

pipe connected to

indoor/outdoor unit

Additional refrigerant

16’5” - 98’5”

(5 - 30 m)

None

*98’5” - 164’1”

(30 - 50 m)

Add 0.43 oz/ft (40 g/m) of

refrigerant for piping that exceeds

98’5” (30 m) up to 164’1” (50 m).

Model RAV-

SP240

Power supply

208/230 V, 60 Hz

MCA

24 A

MOCP (MAX Fuse/CB)

40 A

Breaker

25 A

System interconnection wires

AWG12

MCA = Minimum Circuit Amps

MOCP =Maximum Over Protection Device Amps.