Pressure Testing Gas Supply
Piping System

Test Pressures In Excess Of 1/2 PSIG
(3.5 kPa)

1.

Disconnect fireplace and its individual
equipment shutoff valve from gas sup-
ply piping system. Pressures in excess of
1/2 psig will damage fireplace regulator.

2.

Cap off open end of gas pipe where
equipment shutoff valve was connected.

3.

Pressurize supply piping system by ei-
ther using compressed air or opening
propane/LP supply tank valve.

4.

Check all joints of gas supply piping
system. Apply mixture of liquid soap
and water to gas joints. Bubbles form-
ing show a leak.

5.

Correct all leaks at once.

6.

Reconnect heater equipment shutoff
valve to gas supply. Check reconnected
fittings for leaks.

Open

Closed

Equipment
Shutoff
Valve

Figure 27 - Checking Gas Joints Shown with Optional Mantel

CHECKING GAS
CONNECTIONS

Figure 26 - Equipment Shutoff Valve

Equipment
Shutoff
Valve

Propane/LP
Supply Tank

WARNING: Test all gas pip-

ing and connections for leaks
after installing or servicing. Cor-
rect all leaks at once.

WARNING: Never use an open

flame to check for a leak. Apply a
mixture of liquid soap and water
to all joints. Bubbles forming
show a leak. Correct all leaks at
once.

Test Pressures Equal To or Less Than
1/2 PSIG (3.5 kPa)

1.

Close equipment shutoff valve (see
Figure 26).

2.

Pressurize supply piping system by ei-
ther using compressed air or opening
propane/LP supply tank valve.

3.

Check all joints from propane/LP sup-
ply tank to equipment shutoff valve (see
Figure 27). Apply mixture of liquid
soap and water to gas joints. Bubbles
forming show a leak.

4.

Correct all leaks at once.

Pressure Testing Fireplace Gas
Connections

1.

Open equipment shutoff valve (see
Figure 26).

2.

Open propane/LP supply tank valve.

3.

Make sure control knob of fireplace is
in the OFF position.

4.

Check all joints from equipment shutoff
valve to thermostat gas valve (see Fig-
ure 27). Apply mixture of liquid soap
and water to gas joints. Bubbles form-
ing show a leak.

5.

Correct all leaks at once.

6.

Light fireplace (see Operating Fire-
place
, pages 18 through 20). Check all
other internal joints for leaks.

7.

Turn off fireplace (see To Turn Off Gas
to Appliance
, page 19).

8.

Replace front panel.

INSTALLATION

Continued

CAUTION: Make sure external

regulator has been installed be-
tween propane/LP supply and fire-
place. See guidelines under

Con-

necting to Gas Supply, page 13.