VistaQuest N7227V5 User Manual

Page 50

Advertising
background image

– 50 –

This control complies with NFPA requirements for temporal pulse
sounding of fire notification appliances.

Temporal pulse sounding for a fire alarm consists of the following:
3 pulses – pause – 3 pulses – pause – 3 pulses. . . repeated.

Sounder Connections

The VISTA–10SE provides a 12 VDC output which can power external alarm
sounders ( bells or sirens , see compatible sounders listed previously). This
output will activate a sounder when an alarm occurs.
Make connections to alarm output terminals 3 (+) and 4 (). See Figure 11.

3

4

ALARM
OUTPUT

CONTROL BOARD

+

+

No. 702

SIREN

Figure 11. Typical Sounder Wiring

Programming for External Sounders

1.

With at least one 2-line Alpha keypad ( 5137AD or 6139) connected to the
keypad terminals on the control, power up the system temporarily. If you
had previously connected the AC transformer to the control panel, you
need only plug in the transformer (to 120VAC outlet) to power up the
system.

2.

Enter the programming mode by keying the following on the Alpha keypad:
INSTALLER code (4 1 1 1) + 8 + 0.

3.

Press

28. Single Alarm Sounding per Zone/Armed Period .

Enter “1” for yes, “0” for no (default).

4.

Press

29. Fire Sounder Timeout.

Enter “1” for no timeout, “0” for timeout (default).

5.

Press

30. Alarm Bell Timeout.

Enter 0 for no timeout, 1 for 4 min (default), 2 for 8 min, 3 for 12 min,
4 for 16 min.

6.

Press

51. Confirmation of Arming Ding.

Enter “0” for no (default), “1” for yes, “2” for yes, but with RF arming only.

7. Exit the programming mode by entering

99.

Testing the Sounder

After installation of the sounder is completed, the Secu rity System should be
carefully tested, as follows.

1.

Connect the battery wires from the control board to the battery, observing
correct polarity.

2.

Enter the INSTALLER code (4 1 1 1) and press the TEST key on the wired
keypad.
The external sounder should sound for 1 second if the sounder is good and
proper connections have been made. Note that if the backup battery is
discharged, the sounder will not turn on.

3.

To turn off the test mode, enter the INSTALLER code (4 1 1 1) and press
the OFF key.

Advertising