Installation-Wiring

Installation - Wiring, Chapter 3

WATLOW Series 1500 User's Manual

31

Noise Suppression Devices Available from Watlow

Watlow Winona stocks a few key noise suppression parts. You may order these by
calling your local Watlow distributor.

Item

Electrical Ratings

Part Number

Common Mode Line Filter

250V, 3 Amp

0804-0196-0000

Differential Mode Line Filter

Refer to the islatrol listing above.

Metal Oxide Varistor

150V, 80 Joule

0802-0273-0000

MOV

130V, 38 Joule

0802-0304-0000

MOV

275V, 75 Joule

0802-0266-0000

MOV

275V, 140 Joule

0802-0405-0000

Line Filtering Configurations for Controls

These three diagrams show you filter configurations for removing input power noise.
Choose the one best suited for your system if you are unsure which one to use, see
Figure 12.

For very dirty or critical application - use micro-computer-regulated power
supply or Uninterruptable Power Supply (U.P.S.)

Line

Load

L2

L1

Ground

Control

k

1

D.M. Line Filter

Shield

C.M. Line Filter

Line

Load

L2

L1

Ground

k

1

D.M. Line Filter

k

2

mov

Line

Load

L2

L1

Ground

Control

k

1

C.M. Line Filter

k

2

Shield

Figure 10 -
Differential Mode
Filter Diagram

Figure 11 -
Common Mode
Filter Diagram

Figure 12 -
Combination
Differential-
Common Mode
Filter Diagram

1

Keep filters 12
inches or less from
the control. Mini-
mize the line
distance where
noise can be re-
introduced to
control.

2

To prevent ground
loops do not fasten
common mode line
filters or filters with
metal cases to metal
that is at ground
potential. Doing so
will reduce filter
effectiveness.

Table 4 -
Noise Suppres-
sion Device
Ratings