Watlow Electric Ramping and Profiling Microprocessor-Based Control SERIES 1500 User Manual

Page 88

Advertising
background image

Restart:

RTD:

Set

point:

Signal

conditioner:

Single .mode
cont
rol :

Span:

Switching
sensltlvlty:

Thermal system:

Thermocouple:

Thermocouple

break

protection:

Three mode control:

Time-In-step:

Time Proportioning

Control:

Trlac:

Solid state switching device.

Two posltlon

control:

An ON/OFF control.

Warm

Start:

Start-up condition

where

all program information is remembered by the

instrument’s memory back-up protection.

In the Series 1500, powering up

with

Dip Switch #6 in the OFF position gives a “Warm Start.”

Wet Bulb:

Zero switching:

To begin to control a thermal system again, after stopping control and holding

the process variable at a fixed value. A “restart” may occur with newly-

programmed information in microprocessor-based controls.

Resistance Temperature Detector. Resistive sensing device displaying linear

resistance versus temperature characteristics. Displays positive temperature

coefficient.

Intended value of the process variable.

An electronic circuit that provides sensor compatibility of the input signal for use

in the control. Includes linearization and/or sensor excitiation.

Proportioning control.

Distance in degrees or other units between the minimum and maximum

operating limits of a sensor or controller.

See "Hysteresis."

A regulated environment consisting of a heat source, heat transfer medium,

sensing device and a process variable control instrument.

Temperature sensing device that is constructed of two dissimilar metals
wherein a measurable, predictable voltage is generated corresponding to
temperature.

Fail-safe operation that assures output shutdown upon an open thermocouple

condition.

Proportioning control with auto-reset and rate.

Time remaining in any given program step.

Action which varies the amount of ON and OFF time when “close” to the set

point, i.e., in the proportional band. This variance is the result of the control

algorithm. In other words, the amount of time the output relay is energized
depends on the system control requirement.

Half of a wet bulb/dry bulb

%RH

sensor

system, i.e., an RTD with a wet sock.

Action which provides output switching only at the zero voltage

crossing

points

of the AC line.

88

WATLOW Series 1500 User's Manual

Glossary, Appendix

Advertising