Watlow Electric Ramping and Profiling Microprocessor-Based Control SERIES 1500 User Manual

Page 71

Advertising
background image

Technical Reference

ALM?

Request current alarm code information.

Sample Response:
0018

Note: These alarms are additive and may occur in any combination. To decode, use the following list.

Subtract out the largest possible integer first, then the next largest possible integer, and so on.

The integer 16 is the largest possible integer to subtract out, leaving a remainder of 2.

The integer 2 stands alone. Thus Alarm Codes 16 and 2 are now present in the system.

AlarmCode

0

1

=

*

2

=

*

4

=

*

8

=

*

16

=

32

=

64

=

.

128

=

256

=

.

512

=

Low RAM back-up battery.

Power interrupt.

Ch-1 Actual has exceeded UP, the upper process alarm value.

CH-1

Actual has exceeded LP, the lower process alarm value.

Ch-1 Actual has exceeded Ud, the upper deviation alarm value.

Ch-1 Actual has exceeded Ld, the lower deviation alarm va!ue.
Ch-2 Actual has exceeded UP, the upper process alarm value.

Ch-2 Actual has exceeded LP, the lower process alarm value.
Ch-2 Actual has exceeded Ud, the upper deviation alarm value.

Ch-2 Actual

has exceeded Ld,

the lower deviation alarm value.

ALM 00

Clear all alarm conditions now occurring.

Sample Transmission:
ALM 00

NXS --

Put

the Series 1500

into

Step - - now.

Sample Transmission:

NXS 25

ERR?

Request the last communcation error code

and clear the error code register to 0.

Error codes are listed in the Error Code section following this one.

Sample Response:

0111

Data Communications, Commands and Syntax, Chapter

4 WATLOW Series 1500 User's Manual 71