Troubleshooting

189

Critical Error Occurred Prior to this Power-Up

Audible Beeps: None

Possible Cause: A catastrophic system error, which caused the server to crash,
has been logged.

Action: Run Insight Diagnostics ("HP Insight Diagnostics" on page

80

) and

replace failed components as indicated.

Fan Solution Not Fully Redundant

Audible Beeps:

Possible Cause: The minimum number of required fans are installed, but some
redundant fans are missing or failed.

Action: Install fans or replace failed fans to complete redundancy.

Fan Solution Not Sufficient

Audible Beeps:

Possible Cause: The minimum number of required fans are missing or failed.

Action: Install fans or replace any failed fans.

Fatal DMA Error

Audible Beeps: None

Possible Cause: The DMA controller has experienced a critical error that has
caused an NMI.

Action: Run Insight Diagnostics and replace failed components as indicated.