York AHP18 THRU 60 User Manual

Page 11

Advertising
background image

255029-YTG-J-1007

Unitary Products Group

11

COOLING MODELS WITH ELECTRIC HEAT WIRING

*

Optional dehumidification humidistat switch contacts open on humidity rise.

Notes:
1. “Y” Terminal on Air Handler Control Board must be connected for full CFM and applications requiring 60 second blower off delay for SEER

enhancement.

2. Move HUM STAT Jumper on AH Control Board to YES position if Humidistat is used.
3. MODE Jumper on AH control board should be set to A/C for air conditioners.

*

Optional dehumidification humidistat switch contacts open on rise.

Notes:
1. “Y” Terminal on Air Handler Control Board must be connected for full CFM and applications requiring 60 second blower off delay for SEER

enhancement.

2. Move HUM STAT Jumper on AH Control Board to YES/NO position.
3. MODE Jumper on AH control board should be set to HP for heat pumps.
4. To change quantity of heat during HP defrost cycle - Reverse connections at W1 & W2 on Air Handler Control Board.

COOLING MODELS WITH ELECTRIC HEAT WIRING

MA SERIES - Air Handler Control Wiring

Typical A/C - Cooling only Applications

THERMOSTAT

AIR HANDLER

BOARD

1 - STAGE

AIR CONDITIONING

R

R

G

Y

W1

W2

C

G

W1

W2

Y

C

Y / Y2

Y1

O

HUM

X / L

COM

HUMIDISTAT *

THERMOSTAT

AIR HANDLER

BOARD

1 - STAGE

AIR CONDITIONING

R

R

G

Y

W1

W2

C

G

W1

W2

Y

C

Y / Y2

Y1

O

HUM

X / L

COM

HUMIDISTAT *

MA SERIES - Air Handler Control Wiring

Typical A/C with Electric Heat Applications

SINGLE-STAGE COOLING WIRING

THERMOSTAT

AIR HANDLER

BOARD

HEAT PUMP

R

R

R

G

G

Y

W / W1

O

W

O

O

C

X / L

X / L

C

Y / Y2

Y1

Y

W1 66

W2

W1

HUM

COM

HUMIDISTAT *

W2

E

X / L

And Newer UPG Single Stage HP Systems

Single Stage H/P with Standard Demand Defrost Control Board

CONTROL WIRING - AHP or MA Series Air Handler

Advertising