York AHP18 THRU 60 User Manual

Page 4

Advertising
background image

255029-YTG-J-1007

4

Unitary Products Group

ACCESSORIES

Refer to Price Manual for specific model numbers.

TXV Kits - TXV kits are available for “Flex-coil” applications
and converting R22 to R410A or as a service replacement.
All kits are bolt-on and require no brazing to install.

Non-Combustible Bases - A combustible floor base acces-
sory is available, if required by local codes, when the air han-
dler is installed in the downflow position on a combustible
material.

Electric Heaters - 4HK models shown under electrical data
include sequential operation and temperature dual limit
switches for safe, efficient operation. Circuit breakers are pro-
vided where shown.

External Insulating Wrap Kit - Provides a vinyl covered
thermal insulation wrap, providing additional thermal insula-
tion protection to prevent sweating in applications where
extreme high humidity is present. Air Handler cover (or wrap)
has Velcro edges for easy installation and access.

LIMITATIONS

These units must be wired and installed in accordance with
all national and local safety codes.

Voltage limits are as follows:

Airflow must be within the minimum and maximum limits
approved for electric heat, evaporator coils and outdoor units.

All Air handler units are UL Listed up to 0.50" w.c. external static pressure, including air filter, wet coil, and largest KW size heater, unless otherwise
noted

.

Air Handler

Voltage

Voltage

code

1

Normal Operating

Voltage Range

1. Rated in accordance with ARI Standard 110, utilization range “A”.

208/230-1-60

06

187-253

220/240-1-50

93

198-264

Entering Air Temperature Limits

Wet Bulb Temp.°F

Dry Bulb Temp. °F

Min.

Max.

Min.

Max.

57

72

65

95

AIR FLOW DATA - 60 Hz MODELS

Models

Blower

Motor

Speed

208 Volt

CFM

1

@ External Static Pressure - IWC

0.10

0.20

0.30

0.40

0.50

0.60

0.70

0.80

0.90

1.00

AHP18B**(N,H)21

High

1142

1096

1053

997

925

828

721

210

N/A

N/A

Medium

677

652

634

615

572

486

295

120

N/A

N/A

Low

442

427

395

361

289

209

114

N/A

N/A

N/A

AHP24B**(N,H)21

High

1084

1038

985

935

856

762

665

602

484

333

Medium

840

807

767

693

610

550

485

387

323

221

Low

654

614

548

483

420

349

302

218

179

130

AHP30B**(N,H)21

High

1244

1184

1138

1079

1004

903

841

674

580

457

Medium

956

913

868

815

748

663

574

487

384

N/A

Low

941

904

862

806

731

643

566

480

361

226

AHP36C**(N,H)21

High

1719

1650

1572

1482

1386

1273

1108

925

785

644

Medium

1119

1097

1062

1019

935

827

743

637

479

337

Low

929

910

877

825

760

685

616

508

372

221

AHP42C**(N,H)21

High

1719

1650

1572

1482

1386

1273

1108

925

785

644

Medium

1119

1097

1062

1019

935

827

743

637

479

337

Low

929

910

877

825

760

685

616

508

372

221

AHP48D**(N,H)21

SHP48D**N21

High

1941

1818

1675

1532

1269

870

703

362

146

N/A

Medium

1594

1474

1409

1260

1021

802

524

215

144

N/A

Low

1241

1204

1128

1014

819

659

385

165

N/A

N/A

AHP60D**(N,H)21

SHP60D**N21

High / #1

2126

2093

2074

2048

1991

1941

1801

1569

1461

1366

Medium High / #2

1863

1842

1804

1800

1758

1730

1662

1503

1383

1306

Medium / #3

1642

1603

1593

1568

1523

1471

1410

1334

1307

1216

Medium Low / #4

1482

1468

1427

1370

1324

1274

1233

1196

1153

1099

Low / #5

1268

1220

1169

1118

1070

1037

982.5

949.1

891.9

831

1. Includes return air filter and coil.

Advertising