255029-YTG-J-1007

Unitary Products Group

5

All air handler units are UL Listed up to 0.50" w.c. external static pressure, including air filter, wet coil, and largest KW size heater, unless otherwise
noted.

AIR FLOW DATA - 60 Hz MODELS

Models

Blower

Motor

Speed

230 Volt

CFM

1

@ External Static Pressure - IWC

0.10

0.20

0.30

0.40

0.50

0.60

0.70

0.80

0.90

1.00

AHP18B**(N,H)21

High

1054

989

923

862

791

665

581

202

N/A

N/A

Medium

782

762

716

670

613

536

315

121

N/A

N/A

Low

541

519

479

445

397

298

168

N/A

N/A

N/A

AHP24B**(N,H)21

High

1232

1167

1098

1025

940

826

731

622

486

345

Medium

966

915

868

799

724

641

540

452

347

224

Low

785

740

684

618

532

446

364

296

192

131

AHP30B**(N,H)21

High

1434

1359

1297

1220

1138

1050

916

782

640

519

Medium

1112

1076

1031

970

907

802

629

507

394

380

Low

885

854

821

751

686

625

547

459

350

N/A

AHP36C**(N,H)21

High

1760

1681

1607

1538

1456

1360

1322

1260

966

770

Medium

1320

1284

1255

1207

1146

1075

988

846

729

572

Low

1146

1119

1090

1038

992

972

841

725

617

496

AHP42C**(N,H)21

High

1883

1764

1657

1543

1435

1327

1210

902

714

527

Medium

1625

1510

1429

1339

1256

1172

1038

765

609

412

Low

1260

1225

1179

1110

1047

973

785

638

500

340

AHP48D**(N,H)21

SHP48D**N21

High

2029

1944

1837

1743

1643

1537

1435

1320

1064

789

Medium

1805

1730

1649

1566

1479

1385

1286

1147

851

683

Low

1491

1441

1388

1328

1253

1174

1076

867

726

555

AHP60D**(N,H)21

SHP60D**N21

High / #1

2256

2226

2198

2159

2095

1959

1914

1776

1519

1380

Medium High / #2

1990

1963

1935

1893

1857

1820

1783

1698

1486

1353

Medium / #3

1774

1748

1704

1670

1635

1593

1534

1480

1384

1325

Medium Low / #4

1557

1523

1483

1432

1389

1329

1265

1235

1198

1167

Low / #5

1340

1300

1253

1198

1126

1079

1037

1007

954

912

1. Includes return air filter and coil.

APPLICATION FACTORS - RATED CFM VS. ACTUAL CFM

% Of Rated Airflow

80%

90%

Rated CFM

110%

120%

Capacity Factor

0.96

0.98

1.00

1.02

1.03