May be 0 (no breaker) or 1 (with breaker).

ELECTRICAL DATA (FOR SINGLE SOURCE POWER SUPPLY) - COPPER WIRE 208/230-1-60

Models

Heater

Models*

Heater

Amps

240V

Field Wiring

Min. Circuit Ampacity

Max. O.C.P.

1

Amps/Type

75°C Wire Size - AWG

208V

240V

208V

240V

208V

240V

AHP18B**(N,H)21

4HK*6500206

10.4

13.5

15.4

15

20

12

12

4HK*6500506

20.0

23.8

27.4

25

30

10

10

4HK*6500806

31.3

36.0

41.5

40

45

8

8

AHP24B**(N,H)21

4HK*6500206

10.4

13.0

14.9

15

15

12

12

4HK*6500506

20.0

23.4

26.9

25

30

10

10

4HK*6500806

31.3

35.6

41.0

40

45

8

8

4HK*6501006

40.0

45.1

51.9

45

60

8

6

4HK16501306

54.2

60.4

69.6

70

70

4

4

AHP30B**(N,H)21

4HK*6500506

20.0

24.2

27.8

25

30

10

10

4HK*6500806

31.3

36.4

41.9

40

45

8

8

4HK*6501006

40.0

45.8

52.8

50

60

8

6

4HK16501306

54.2

60.1

70.5

70

90

4

3

4HK165N1506

60.0

67.5

77.8

70

90

4

3

AHP36C**(N,H)21

4HK*6500506

20.0

25.8

29.5

30

30

10

10

4HK*6500806

31.3

38.0

43.6

40

45

8

8

4HK*6501006

40.0

47.5

54.5

50

60

8

6

4HK16501506

60.0

69.1

79.5

70

90

4

3

4HK16501806

73.3

83.6

96.1

90

100

3

3

AHP42C**(N,H)21

4HK*6500506

20.0

25.9

29.8

30

30

8

8

4HK*6500806

31.3

38.1

43.9

40

45

8

8

4HK*6501006

40.0

47.6

54.8

50

60

6

6

4HK16501506

60.0

69.3

79.8

70

90

4

3

4HK16501806

73.3

83.7

96.4

90

100

3

3

4HK16502006

80.0

90.9

104.8

100

110

3

2

AHP48D**(N,H)21

SHP48D**N21

4HK*6500506

20.0

25.9

29.8

30

30

10

10

4HK*6500806

31.3

38.1

43.9

40

45

8

8

4HK*6501006

40.0

47.6

54.8

50

60

8

6

4HK16501506

60.0

69.3

79.8

70

90

4

3

4HK16501806

73.3

83.7

96.4

90

100

3

3

4HK16502006

80.0

90.9

104.8

100

110

3

2

AHP60D**(N,H)21

SHP60D**N21

4HK*6500506

20.0

31.2

34.5

35

35

8

8

4HK*6500806

31.3

43.4

48.6

45

50

8

8

4HK*6501006

40.0

52.8

59.5

60

60

6

6

4HK16501506

60.0

74.5

84.5

90

90

3

3

4HK16501806

73.3

88.9

101.1

90

110

3

2

4HK16502006

80.0

96.2

109.5

100

125

3

1

4HK16502506

100.0

117.8

134.5

125

150

1

1/0