York AHP18 THRU 60 User Manual

Page 3

Advertising
background image

255029-YTG-J-1007

Unitary Products Group

3

COOLING CAPACITY

Models

Rated CFM

Entering Air °F

(Dry / Wet Bulb)

MBH@ Evaporator Temperature and Corresponding Pressure °F / PSIG

35 / 61.5

40 / 68.5

45 / 76.0

50 / 84.0

FULL-CASED “A” TYPE MULTI-POSITION

AHP18B2A(N,H)21

650

85/72

24.5

22.3

19.9

17.3

80/67

22.6

20.3

18.0

15.6

75/62

18.5

16.4

14.2

12.0

70/57

15.0

13.1

10.9

8.5

AHP24B2A(N,H)21

800

85/72

35.0

31.8

28.4

24.7

80/67

32.2

29.1

25.7

22.3

75/62

26.4

23.4

21.0

17.1

70/57

21.4

18.6

20.2

12.1

AHP30B2A(N,H)21

1050

85/72

41.5

37.8

33.7

29.5

80/67

36.2

32.4

28.6

24.5

75/62

29.1

25.3

24.0

19.2

70/57

24.1

21.5

18.7

15.8

AHP36C2A(N,H)21

1200

85/72

51.3

46.7

41.7

36.8

80/67

41.1

36.3

31.8

27.1

75/62

32.1

27.0

29.4

21.9

70/57

27.6

25.4

23.5

18.3

AHP42C2C(N,H)21

1400

85/72

88.4

76.0

63.3

50.0

80/67

70.8

59.4

48.4

37.0

75/62

55.2

43.9

35.8

29.9

70/57

47.4

41.5

32.37

25.24

AHP48D2C(N,H)21

SHP48D2CN21

1600

85/72

100.5

86.4

72.0

56.8

80/67

80.4

67.5

55.0

42.1

75/62

62.7

49.9

40.7

34.0

70/57

53.9

47.2

36.81

28.71

AHP60D2C(N,H)21

SHP60D2CN21

1850

85/72

119.9

101.0

82.0

62.2

80/67

96.0

79.2

62.6

45.8

75/62

74.8

58.6

46.2

37.0

70/57

64.3

55.4

43.2

33.7

Advertising