TABLE 21 -

ADDITIONAL STATIC PRESSURE RESISTANCE

FIG. 3 - CLEARANCES

DESCRIPTION

RESISTANCE, IWG

CFM

500

600

700

800

900

1,000 1,100 1,200 1,300 1,400 1,500 1,600 1,700 1,800 1,900 2,000

Wet Indoor coil

0.01

0.01

0.01

0.02

0.01

0.02

0.03

0.04

0.04

0.03

0.04

0.04

0.05

0.05

0.06

0.07

Economizer

0.00

0.00

0.00

0.01

0.01

0.01

0.01

0.02

0.03

0.04

0.05

0.06

0.07

0.07

0.08

0.08

Filter/Frame Kit

0.01

0.02

0.02

0.02

0.02

0.02

0.03

0.03

0.03

0.03

0.04

0.05

0.05

0.06

0.06

0.07

Electric Heat

0.02

0.03

0.03

0.03

0.04

0.04

0.05

0.06

0.07

0.08

0.09

0.10

0.01

0.11

0.11

0.12

NOTE: 1. Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table.

2. The pressure thru the economizer is greater for 100% outdoor air then for 100% return air. If the resistance of the return air duct system is less then 0.25 IWG, the unit will deliver

less CFM during full economizer operation.

CLEARANCES

(Minimum)

Front

12"

Back

0"

Left Side (Filter Access) 24"

Right Side

24"

Below Unit

Q

0"

Above Unit

R

36" (For Condenser

Air Discharge)

Q

Units may be installed on combustible floors made from wood or class A,

B or C roof covering material.

R

Units must be installed outdoors. Overhanging structures or shrubs

should not obstruct outdoor air discharge outlet.

3'

M IN IM UM C LEARANCE O F 1 "

ALL S ID ES F O R T H E F IR ST 3 '

O F D UCT F O R 2 0 & 2 5 k W .

ZERO IN CHES T HER EAFTER,

FO R A LL O TH ER H EATERS,

ZERO IN CH C LEARANCE A LL

SID ES F O R E N TIRE L EN G TH

O F D UCT.

FLEXIB LE D U CT

CO LLAR

NOTE: FOR UNITS APPLIED WITH A ROOF

CURB, THE MINIMUM CLEARANCE MAY BE

REDUCED FROM 1 INCH TO 1/2 INCH BE-

TWEEN COMBUSTIBLE ROOF CURB MA-

TERIAL AND THE SUPPLY DUCT.