NORMAL MAINTENANCE

WARNING: Prior to any of the following maintenance proce-

dures, shut off all power to the unit, to avoid per-
sonal injury.

Periodic maintenance consists of changing or cleaning filters
and general cleaning of the outdoor coil.

FILTERS - Inspect once a month. Replace Disposable or
clean Permanent Type as necessary. DO NOT replace Per-
manent Type with Disposable.

MOTORS - Indoor and outdoor fan motors are permanently
lubricated and require no maintenance.

OUTDOOR COIL - Dirt should not be allowed to accumulate
on the outdoor coil surface or other parts in the air circuit.
Cleaning should be as often as necessary to keep the coil
clean. Use a brush, vacuum cleaner attachment, or other
suitable means. If water is used to clean the coil, be sure
that the power to the unit is shut off prior to cleaning.

CAUTION: Exercise care when cleaning the coil so that the

coil fins are not damaged.

Do not permit the hot condenser air discharge to be
obstructed by overhanging structures or shrubs.

MAINTENANCE

TABLE 23 - THERMOSTAT SIGNALS (THREE PHASE UNITS)

SIGNAL

STATE

BOARD FUNCTION

“G”

ON

FAN INSTANT ON

OFF

FAN INSTANT OFF

“G” & “Y” & “O”

ON

FAN INSTANT ON
COMPRESSOR AND OUTDOOR FAN INSTANT ON (AFTER ANTI-SHORT CYCLE DELAY)
REVERSING VALVE ENERGIZED
SYSTEM OPERATES IN COOLING

OFF

COMPRESSOR AND OUTDOOR FAN INSTANT OFF
FAN 60 SEC. DELAY OFF

“G” & “Y”

ON

FAN INSTANT ON
COMPRESSOR AND OUTDOOR FAN INSTANT ON (AFTER ANTI-SHORT CYCLE DELAY)
SYSTEM OPERATES IN HEATING

OFF

COMPRESSOR AND OUTDOOR FAN INSTANT OFF
FAN 60 SEC. DELAY OFF

“G” & “W”

ON

FAN INSTANT ON
HEATER BANK 1, 2 & 3 ELEC. HEAT INSTANT ON
HEATER BANK 4, 5 & 6 ELEC. HEAT 10 SEC. DELAY ON

OFF

HEATER BANK 4, 5 & 6 ELEC. HEAT INSTANT OFF
HEATER BANK 1, 2 & 3 ELEC. HEAT



SEC. DELAY OFF

FAN 10 SEC. DELAY OFF

“G” & “Y” & “W”

ON

FAN INSTANT ON
COMPRESSOR AND OUTDOOR FAN INSTANT ON
SYSTEM OPERATES IN HEATING
HEATER BANK 1, 2 & 3 ELEC. HEAT INSTANT ON
HEATER BANK 4, 5 & 6 ELEC. HEAT 10 SEC. DELAY ON

OFF

COMPRESSOR AND OUTDOOR FAN INSTANT OFF
HEATER BANK 4, 5 & 6 ELEC. HEAT INSTANT OFF
HEATER BANK 1, 2 & 3 ELEC. HEAT



SEC. DELAY OFF

FAN 60 SEC. DELAY OFF

“W”

ON

FAN INSTANT ON
HEATER BANK 1, 2 & 3 ELEC. HEAT INSTANT ON
HEATER BANK 4, 5 & 6 ELEC. HEAT 10 SEC. DELAY ON

OFF

HEATER BANK 4, 5 & 6 ELEC. HEAT INSTANT OFF
HEATER BANK 1, 2 & 3 ELEC. HEAT



SEC. DELAY OFF

FAN 10 SEC. DELAY OFF