Installation – York B1HH018 User Manual

Page 2

Advertising
background image

LIMITATIONS

These units must be installed in accordance with the following
national and local safety codes.

1. National Electrical Code ANSI/NFPS No. 70 or Canadian

Electrical Code Part 1, C22.1 (latest editions).

2. Local plumbing and waste water codes and other applica-

ble local codes.

Refer to Table 1 for unit application data and to Table 5 for elec-
tric heat application data.

If components are to be added to a unit to meet local codes, they
are to be installed at the dealer's and/or the customer's expense.

Size of unit for proposed installation should be based on heat
loss/heat gain calculations made in accordance with industry
recognized procedures identified by the Air Conditioning Con-
tractors of America.

LOCATION

Use the following guidelines to select a suitable location for
these units.

1. Unit is designed for outdoor installation only.

2. Condenser must have an unlimited supply of air. Where a

choice of location is possible, position unit on either north or
east side of building.

3. For ground level installation, a level pad or slab should be

used. The thickness and size of the pad or slab used should
meet local codes and unit weight. Do not tie the slab to the
building foundation.

4. For roof top installation, be sure the structure can support

the weight of the unit plus any field installed components.
Unit must be installed on a level roof curb or appropriate an-
gle iron frame providing adequate support under the com-
pressor/condenser section.

5. Maintain level tolerance of unit to 1/8" maximum.

RIGGING OR HANDLING

Care must be exercised when moving the unit. Do not remove
any packaging until the unit is near the place of installation.
Rig unit with slings placed under the unit. Spreader bars of
sufficient length should be used across the top of the unit.

BEFORE LIFTING A UNIT, MAKE SURE THAT ITS WEIGHT
IS DISTRIBUTED EQUALLY ON THE CABLES SO THAT IT
WILL LIFT EVENLY.

Units may also be moved or lifted with a fork-lift. Slotted
openings in the skid are provided for this purpose. Forks
must pass completely through the base.

Refer to Table 2 for unit weights and to Figure 1 for approxi-
mate center of gravity.

66297-YIM-C-0205

2

Unitary Products Group

B

1

H

H

A

PRODUCT NOMENCLATURE

PRODUCT GENERATION

1 = NEW or Current Design

PRODUCT CATEGORY

B = Single Package Heat Pumps

(Air Cooled)

PRODUCT IDENTIFIER

HH = Heat Pump (12 SEER)

2

0

4

0

6

FACTORY

INSTALLED ELECTRIC HEAT

A = No Electric Heat Installed

VOLTAGE CODE

06 = 208/230-1-60
25 = 208/230-3-60
46 = 460-3-60
58 = 575-3-60

NOMINAL COOLING

CAPACITY (MBH)

018 = 18,000 BTUH 042 = 42,000 BTUH
024 = 24,000 BTUH 048 = 48,000 BTUH

030 = 30,000 BTUH 060 = 60,000 BTUH

036 = 36,000 BTUH

INSTALLATION

Voltage Variation

Min. / Max

.1

208/230V

3

187 / 253

3

460V

414 / 504

575V

518 / 630

Wet Bulb Temperature (

°

F) of Air on

Evaporator Coil, Min. / Max.

57 / 72

Dry Bulb Temperature (

°

F) of Air on

Condenser Coil, Min.

2

/ Max.

45 / 120

1

Rated in accordance with ARI Standard 110, utilization range “A”.

2

A low ambient accessory is available for operation down to 0

°

F

3

“T1" transformer primary tap must be moved from the 230 volt connection to the 208 volt

connection for low voltage applications of 208 volt and below.

TABLE 1 - UNIT APPLICATION DATA

FIG. 1 - CENTER OF GRAVITY

"'



&

26

"%

"

CENTER OF GRAVITY

FRONT

OF

UNIT

“A”

“B”

“C”

“D”

23½

UNIT

SIZE

SHIPPING

WEIGHT

(lbs.)

OPERAT-

ING

WEIGHT

(lbs.)

CORNER WEIGHTS

(location, lbs.)

“A”

“B”

“C”

“D”

018

351

346

103

92

73

83

024

356

351

97

93

81

84

030

353

348

96

93

81

84

036

388

383

106

102

89

92

042

440

435

120

115

101

104

048

485

480

132

127

111

115

060

495

490

135

130

113

117

TABLE 2 - UNITS WEIGHTS