York D*V User Manual

Page 19

Advertising
background image

DATE:

DESCRIPTION:

"DPV" SERIES VERTICAL INDOOR SYSTEM

GENERAL MECHANICAL SPECIFICATIONS

GENERAL

All models 5-15 tons ship as factory-charged unitized packages. The 20 ton model shall be shipped as

separate evaporator and condensing unit modules (nitrogen holding charge only). All units may be field

split and installed as separate modules to suit on-site requirements. All packages are designed for free-

standing mounting on the floor, or on a field fabricated structural steel stand. The 5, 8, and 10 ton models

are shipped with vertical evaporator fan discharge as standard. The 12, 15, and 20 ton models are

shipped horizontal discharge as standard.

CABINET

All cabinets are completely constructed of heavy gauge galvanized steel. The entire unit interior ( both

evaporator and condensing section ) is insulated with 1/2" thick, 2 lb. density insulation. Service panels

are equipped with lifting handles for ease of removal and handling. Duct flanges for condenser discharge,

condenser intake, and evaporator discharges, are provided with the unit for field installation. Duct flange

on evaporator return is incorporated into the filter frame.

COMPRESSORS

All models utilize "Scroll" type hermetic compressors. Compressors are mounted on rubber isolators to

minimize vibration transmission. Internal overload protection is provided. External high pressure and low

pressure cutout switches are included in each compressor control circuit. Crankcase heaters are

standard on all models.

REFRIGERANT CIRCUITS

The 5 ton units have a single refrigeration circuit. The 8-20 ton units feature two independent refrigeration

circuits. Each refrigeration circuit includes an adjustable thermal expansion valve (with external

equalizer), liquid line filter drier, sight glass/moisture indicator, and service gauge ports.

EVAPORATOR AND CONDENSER COILS

The evaporator and condenser coils are constructed of internally enhanced copper tubes mechanically

bonded to rippled aluminum plate fins. Both coils are employed in a draw-thru configuration. Large

evaporator coil face area minimizes potential water blow-off.

INDOOR/OUTDOOR FANS

Forward curved, double inlet and double width centrifugal blowers are used for both evaporator and

condenser air movement. Blower wheels are fabricated of galvanized steel. Blowers employ solid steel

shafts, supported in permanently lubricated ball bearing. All blowers are belt driven. Variable-pitch motor

sheaves allow for field adjustment of blower rpm.

ELECTRICAL/CONTROLS

All units are completely factory wired with all necessary controls. Manual reset protection is provided on

both evaporator and condenser motors. A manual reset circuit is also provided on each compressor

control circuit in the event of high/low pressure cutout. A 24 volt control circuit, with oversize transformer,

is provided for field connection.

FILTERS

All models are shipped with 2-inch thick medium-efficiency throwaway filters factory installed. Filter rack

is external to the cabinet (shipped loose).

Johnson Controls maintains a continuous product improvement policy, therefore specifications are subject to change without notice.

March 2008

MECHANICAL SPECIFICATIONS

DPV240 VERTICAL UNIT

AIR-COOLED SELF-CONTAINED

Form YK145.12-PA8 (308)

2 of 4

Page 19