Technical information, Page 124 – Xantrex Technology SW Series User Manual

Page 132

Advertising
background image

TECHNICAL INFORMATION

Page

124

2001 Xantrex Technology, Inc.

5916 - 195th Street N. E.
Arlington, WA 98223

Telephone: 360/435-8826

Fax: 360/435-2229

www.traceengineering.com

SW Series Inverter/Charger

Part No. 2031-5

Rev. C: February 2001

SETUP MENU – 12 VDC (120 VAC/60HZ) MODELS

To access the SETUP MENU, press the RED and GREEN buttons on your CONTROL PANEL (or
SWRC) at the same time. To exit the Setup Menu, press the ON/OFF MENU button or use the down
MENU HEADING button until you reach the USER MENU (menu headings 1 – 8)

.

MENU HEADING

MENU ITEM

SELECTION

RANGE

DEFAULT

SETTINGS

USER

SETTINGS

Inverter Setup

9

Set Grid Usage

FLT SELL SLT LBX

FLT

Set Low Battery cut out VDC

0.80 – 25.5

11.0

Set LBCO delay minutes

00 - 255

15

Set Low battery cut in VDC

00.0 – 16.5

13.0

Set High battery Cut Out VDC

00.0 – 16.5

16.0

Set search watts

00 - 240

48

Set search spacing

00 – 255

59

Battery Charging

10

Set Bulk volts DC

10.0 – 16.0

14.4

Set Absorption time h:m

00:00 – 23:50

02:00

Set Float volts DC

10.0 – 16.0

13.4

Set Equalize volts DC

10.0 – 16.0

14.4

Set Equalize time h:m

00:00 – 23:50

02:00

Set Max Charge amps AC

01 - 25

20

Set Temp Comp

LeadAcid Nicad

LeadAcid

AC Inputs

11

Set Grid (AC1) amps AC

00 - 63

60

Set Gen (AC2) amps AC

00 - 63

30

Set Input lower limit VAC

80 - 111

108

Set Input upper limit VAC

128 - 149

132

Gen Auto Start Setup

12

Set Load Start amps AC

00 - 63

33

Set Load Start delay min

00.0 – 25.5

05.0

Set Load Stop delay min

00.0 – 25.5

05.0

Set 24 hr start volts DC

05.0 – 25.5

12.3

Set 2 hr start volts DC

05.0 – 16.5

11.8

Set 15 min start volts DC

05.0 – 16.5

11.3

Read LBCO 30 sec start VDC

05.0 – 16.5

11.0

Set Exercise period days

00 - 255

30

Set Maximum run time h:m

00:00 – 23:50

08:00

Gen Starting Details

13

Set RY7 Function

GlowStop Run

Run

Set Gen warmup seconds

16 - 255

60

Set Pre Crank seconds

00 - 255

10

Set Max Cranking seconds

01 - 15

10

Set Post Crank seconds

00 - 255

30

Auxiliary Relays R9 R10

14

Set Relay 9 volts DC

00.0 – 16.5

14.5

R9 Hysteresis volts DC

00.1 – 12.8

01.0

Set Relay 10 volts DC

00.0 – 16.5

14.8

R10 Hysteresis volts DC

00.1 – 12.8

01.0

Set Relay 11 volts DC

00.0 – 16.5

15.0

R11 Hysteresis volts DC

00.1 – 12.8

01.0

Bulk Charge Trigger Timer

15

Start Bulk Time H:M

00:00 – 23:50

00:00

Low Battery Transfer (LBX) 16

Set Low Battery transfer VDC

05.0 – 16.5

11.3

Set Low Battery cut in VDC

05.0 – 16.5

13.0

Battery Selling

17

Set Battery Sell volts DC

10.0 – 16.0

13.4

Set Max Sell amps AC

01 - 25

30

Grid Usage Timer

18

Set Start Charge time h:m

00:00 – 23:50

21:00

End Stop Charge time h:m

00:00 – 23:50

21:00