Installation, Page 19 – Xantrex Technology SW Series User Manual

Page 27

Advertising
background image

INSTALLATION

2001 Xantrex Technology, Inc.

5916 - 195th Street N. E.
Arlington, WA 98223

Telephone: 360/435-8826

Fax: 360/435-2229

www.traceengineering.com

SW Series Inverter/Charger

Part No. 2031-5

Rev. C: February 2001

Page

19

Note: The three neutral terminals are common to each other and can be used in any combination or
order. In a residential application, it is often easier to only connect one AC neutral wire to the inverter and
make the other neutral connections at a central point such as in the AC load center, etc. In mobile
installations, the AC system must have the neutral physically isolated from the ground throughout the load
distribution powered by the inverter. The SW Series Inverter/Charger does not include neutral to ground
switching for the AC electrical system. This must be done externally from the inverter. See the NEUTRAL-
TO-GROUND BOND SWITCHING (RV AND MARINE APPLICATIONS)
section on page 27 for more
information.

Figure 9, AC Input/Output Power Connection

Before making any AC connections, make sure that the inverter is disconnected from the battery (or
battery bank). Feed the wires through conduit fittings located on the left side or left bottom side of the
inverter. (Note: Conduit fittings must be purchased separately and are required by code to comply with
residential and commercial installations).

The AC wiring both in and out of the inverter must also be protected from short circuits and overloads by a fuse
or circuit breaker. Consult the NEC or your local code for more information and for other wire sizes. Table 13 on
page 132 gives suggestions for wire sizing. Follow the wiring guide on the circuit board inside the cover plate
(see Figure 9, above). Connect the AC wiring as follows (from front to back when wall mounted):

Table 1, AC Input and Output Wiring Connections

AC CONNECTIONS

AC TERMINAL BLOCK #

WIRE COLOR

PURPOSE

AC HOT IN 1

1b

Black (Hot)

Utility Power

NEUTRAL IN 1

3b

White (Neutral)

Utility Power

AC HOT IN 2

2b

Black (Hot)

Generator

NEUTRAL IN 2

4b

White (Neutral)

Generator

AC HOT OUT

6b

Black or Red (Hot)

AC Loads

NEUTRAL OUT

5b

White (Neutral)

AC Loads

AC Terminal Block

(TB1)

AC IN 2

From

Generator Power

AC OUT

To

AC Loads

AC IN 1

From

Utility Power

1a

1b

2a

2b

3a

3b

4a

4b

5a

5b

6a

6b