Menu system, Page 52 – Xantrex Technology SW Series User Manual

Page 60

Advertising
background image

MENU SYSTEM

Page

52

2001 Xantrex Technology, Inc.

5916 - 195th Street N. E.
Arlington, WA 98223

Telephone: 360/435-8826

Fax: 360/435-2229

www.traceengineering.com

SW Series Inverter/Charger

Part No. 2031-5

Rev. C: February 2001

Set Relay 9
volts DC

14.5

Set Relay 9
volts DC

29.0

Set Relay 9
volts DC

58.0

12 VDC Models

Range: 05.0 to 17.6

24 VDC Models

Range: 10.0 to 35.5

48 VDC Models

Range: 20.0 to 71.0

Sets the voltage trip point for the auxiliary relay number 9. This setting is compensated for the battery
temperature when using the BTS. There is no intentional time delay on the reaction for this setting. This
allows fast response to rapid voltage changes in the system.

R9 Hysteresis
volts DC

01.0

R9 Hysteresis
volts DC

02.0

R9 Hysteresis
volts DC

04.0

12 VDC Models

Range: 00.1 to 12.8

24 VDC Models

Range: 00.1 to 12.8

48 VDC Models

Range: 00.2 to 25.6

The hysteresis setting for relay number 9. There is an intentional 2-second time delay to reduce cycling.

Set Relay 10
volts DC

14.8

Set Relay 10
volts DC

29.5

Set Relay 10
volts DC

59.0

12 VDC Models

Range: 05.0 to 17.6

24 VDC Models

Range: 10.0 to 35.5

48 VDC Models

Range: 20.0 to 71.0

Sets the voltage trip point for the auxiliary relay number 10. This setting is compensated for the battery
temperature when using the BTS. There is no intentional time delay on the reaction for this setting. This
allows fast response to rapid voltage changes in the system.

R10 Hysteresis
volts DC

01.0

R10 Hysteresis
volts DC

02.0

R10 Hysteresis
volts DC

04.0

12 VDC Models

Range: 00.1 to 12.8

24 VDC Models

Range: 00.1 to 12.8

48 VDC Models

Range: 00.2 to 25.6

The hysteresis setting for relay number 10. There is an intentional 2-second time delay to reduce cycling.

Set Relay 11
volts DC

15.0

Set Relay 11
volts DC

30.0

Set Relay 11
volts DC

60.0

12 VDC Models

Range: 05.0 to 17.6

24 VDC Models

Range: 10.0 to 35.5

48 VDC Models

Range: 20.0 to 71.0

Sets the voltage trip point for the auxiliary relay number 11. This setting is compensated for the battery
temperature when using the BTS. There is no intentional time delay on the reaction for this setting. This
allows fast response to rapid voltage changes in the system.

R11 Hysteresis
volts DC

01.0

R11 Hysteresis
volts DC

02.0

R11 Hysteresis
volts DC

04.0

12 VDC Models

Range: 00.1 to 12.8

24 VDC Models

Range: 00.1 to 12.8

48 VDC Models

Range: 00.2 to 25.6

The hysteresis setting for relay number 11. There is an intentional 2-second time delay to reduce cycling.

INFORMATION DISPLAY

The following information is displayed as additional Menu Items.

Close on batt > setpoint. Open on batt < setpoint – hys.
Relays have 2 seconds delay on close, 0.1 sec delay on open.

Advertising