York SPLIT-SYSTEM YHJD18 THRU 60 User Manual

Page 11

Advertising
background image

398612-YTG-B-0608

Johnson Controls Unitary Products

11

CP equals MBH output divided by (total KW input x 3.412).
HSPF (Heating Seasonal Performance Factor) is the total heating output during a normal annual usage period for heating divided by
the total electric power input during the same period.
— = Not Applicable.

13 SEER HP WITH AV / SV / F*FV - VARIABLE SPEED

YHJD18S21S1

AV24

17.0 3.46 1.40 9.0 2.32 1.08 8.00

YHJD24S21S1

AV24

22.0 4.04 1.62 12.0 2.64 1.28 8.40

YHJD30S21S1

AV36

28.0 3.80 2.18 14.0 2.38 1.76 8.00

YHJD36S21S1

AV36

33.0 3.74 2.61 20.0 2.62 2.23 8.80

AV/SV48

33.0 3.74 2.61 20.0 2.62 2.23 8.80

YHJD42S21S1

AV/SV48

40.0 3.68 3.18 24.0 2.74 2.58 8.85

AV/SV60

40.0 3.70 3.20 24.0 2.74 2.58 8.85

F4FV060

40.0 3.70 3.20 24.0 2.74 2.58 8.85

YHJD48S21S1

AV/SV48

48.0 3.50 3.97 37.0 2.82 3.84 8.00

AV/SV60

48.0 3.48 3.99 37.0 2.82 3.84 8.00

F4FV060

48.0 3.48 3.99 37.0 2.82 3.84 8.00

13 SEER HP WITH AHP / SHP / F*FP

YHJD18S21S1

AHP18

17.0 3.26 1.54 9.0 2.18 1.23 7.70

AHP24

17.0 3.28 1.52 9.0 2.18 1.22 7.70

F4FP024

17.0 3.26 1.54 9.0 2.18 1.23 7.70

YHJD24S21S1

AHP24

23.0 3.74 1.80 12.0 2.46 1.45 7.70

AHP30

23.0 3.74 1.80 12.0 2.44 1.46 7.70

F4FP030

23.0 3.74 1.80 12.0 2.46 1.45 7.70

YHJD30S21S1

AHP30

29.0 3.54 2.41 15.0 2.24 1.96 7.65

AHP36

29.0 3.54 2.41 15.0 2.24 1.96 7.65

F4FP040

29.0 3.54 2.41 15.0 2.24 1.96 7.65

YHJD36S21S1

AHP36

34.0 3.58 2.78 21.0 2.52 2.39 8.50

AHP42

34.0 3.60 2.76 20.0 2.52 2.37 8.55

AHP/SHP60

33.0 3.74 2.61 20.0 2.62 2.23 8.80

F4FP045

34.0 3.58 2.78 21.0 2.52 2.39 8.50

F5FP048

33.0 3.74 2.61 20.0 2.62 2.23 8.80

F5FP060

33.0 3.74 2.61 20.0 2.62 2.23 8.80

YHJD42S21S1

AHP/SHP48

42.0 3.56 3.41 25.0 2.64 2.75 8.60

AHP/SHP60

40.0 3.70 3.20 24.0 2.74 2.58 8.85

F4FP045

42.0 3.56 3.41 25.0 2.64 2.75 8.60

F5FP048

40.0 3.70 3.20 24.0 2.74 2.58 8.85

F5FP060

40.0 3.70 3.20 24.0 2.74 2.58 8.85

YHJD48S21S1

AHP/SHP48

48.0 3.40 4.13 37.0 2.74 3.99 7.70

AHP/SHP60

48.0 3.48 3.99 37.0 2.80 3.87 8.00

F5FP060

48.0 3.48 3.99 37.0 2.80 3.87 8.00

1. Rated CFM same as for cooling.
2. Heating MBH based on ARI standards of 70° DB entering indoor air, 72% RH outdoor air with 25 feet of interconnecting piping and

no supplemental electric heat operation.

HEATING PERFORMANCE - With Air Handler (Continued)

UNIT

MODEL*

AIR

HANDLER

COIL

1

MODEL

ARI HEATING

2

47

°F

17

°F

HSPF

MBH

COP

KW

MBH

COP

KW

STD

Advertising