York SPLIT-SYSTEM YHJD18 THRU 60 User Manual

Page 29

Advertising
background image

398612-YTG-B-0608

Johnson Controls Unitary Products

29

Multipliers for determining the performance with other indoor sections.

HEATING PERFORMANCE DATA

CONDENSING UNIT MODEL NO

YHJD60S21S1

EVAPORATOR COIL MODEL NO

FC/MC62

AIR TEMP.

ENTERING

OUTDOOR UNIT

AIR TEMP.

ENTERING

INDOOR COIL

ID CFM

1600

1800

2000

MBTUH

KW

C.O.P.

MBTUH

KW

C.O.P.

MBTUH

KW

C.O.P.

60

60

75.6

4.6

4.8

76.1

4.4

5.1

76.6

4.2

5.3

70

72.9

5.1

4.2

73.4

4.9

4.4

73.8

4.6

4.7

80

70.2

5.6

3.7

70.6

5.3

3.9

71.0

5.1

4.1

47

60

63.8

4.3

4.4

64.2

4.1

4.6

64.7

3.9

4.8

70

61.4

4.8

3.8

61.8

4.6

4.0

62.2

4.4

4.2

80

59.0

5.3

3.3

59.3

5.0

3.4

59.6

4.8

3.6

40

60

53.1

4.0

3.9

53.2

4.2

3.7

53.3

4.3

3.6

70

48.9

4.4

3.3

49.3

4.6

3.1

49.6

4.8

3.0

80

44.7

4.7

2.7

45.4

5.0

2.7

46.0

5.2

2.6

30

60

47.5

4.1

3.4

48.8

3.9

3.6

50.2

3.7

3.9

70

46.6

4.5

3.0

47.3

4.4

3.2

48.1

4.2

3.4

80

45.7

4.9

2.7

45.8

4.8

2.8

45.9

4.6

2.9

17

60

38.3

3.8

2.9

40.1

3.6

3.2

41.9

3.5

3.5

70

36.8

4.0

2.7

38.4

4.0

2.8

40.0

3.9

3.0

80

35.3

4.3

2.4

36.7

4.3

2.5

38.1

4.4

2.6

10

60

33.1

3.4

2.9

34.5

3.5

2.9

36.0

3.6

2.9

70

33.2

3.9

2.5

34.0

3.9

2.5

34.7

3.9

2.6

80

33.4

4.4

2.2

33.4

4.3

2.2

33.4

4.3

2.3

NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.

Air Handler

Coil

MBH

KW

COP

MV20D

FC/MC62D

1.00 1.01 0.99

MA20D

FC/MC62D

1.00 1.00 1.00

Variable Speed
Furnace

Coil

MBH

KW

COP

PV8*C20

FC/MC62D 1.00

1.00

1.00

P(C,V)9*C20

FC/MC62D 0.98

1.00

1.00

P(C,V)9*D20

FC/MC62D 0.96

1.01

0.99

Advertising