Smoke index procedure, B. external pressure probe, Connect the probe to the instrument – RIDGID FG-100 User Manual

Page 7: Insert the probe to the chimney, Press, Ambient temperature probe flue gas probe

Advertising
background image

REMOVE THE PROBE FROM THE STACK

Press:

Press

to select the external Sensor input

F2

Press

“ZERO” to

.

ait for the measure stabilization.

Press

to save the measured value. The v

Press

to exit to the previous menu.

FI

F2

reset the display indication

Insert the probe inside the standard boiler holes (see figure). If the boiler
do not have them, insert the probe at 2 diameter from the boiler and in
central position in the stack
W

alue will printed on the report.

The smoke index can be set.

Connect the external probe to the instrument

ATTENTION:

be sure that the two elements, sensor and probe, are fixed

and in vertical position. Do not move the probe after the zeroing.

3. Smoke index procedure

- applicable for oil burner

REMOVE THE PROBE FROM THE STACK

Press

to input the ambient temperature

Draft can be measured using the external pressure probe.
Do not exceed 0.2 mbar input.

B. External pressure probe

F1=Internal sensor

F2=External sensor

TaE

23.00

INT

EXT

DRAUGHT

Measure

1.0 mbar

Press [ENTER]

To save measure

ZERO

ESCAPE

SMOKE

Meas. 1: -

Oil.Der.: NO

ESCAPE

Meas. 2: -

AVG

Meas. 3: -

-

Press

#

DP

6

To avoid condensation inside the smoke pump, aspirate ambient air
before the gas sample by the fireside (not in the exhaust gas connection
pipe) without using the paper filter. Introduce now the filter in the pump. The
gas sample should be drawn to the center of the combustion gas flux. The
correct gas volume is sampled with 10 uniform suctions from the pump.
Compare the darkening of the filter with the smoke index table.
The smoke index found cannot exceed the ones defined by the current
normative.

We suggested to use a retaining cone during gas sampling.

Select the Test (from 1 to 3) for input, pressing

to confirm the selection.

Enter value ( from 0 to 9) pressing

Execute the steps above for other test in the same way.

Press

to confirm changes.

Press:

Select the “Oil derivative” field for input, pressing

to confirm the selection.

Enter value (Yes or Not) pressing
Press

to confirm changes.

Press

to exit to the previous menu.

Values will printed on the report.

F2

Press:

4. Connect the probe to the instrument

Ambient temperature probe

Flue gas probe

SMOKE

Meas. 1: 3

Oil.Der.: NO

ESCAPE

Meas. 2: 3

AVG

Meas. 3: 2

-

5. insert the probe to the chimney

Insert the probe inside the standard
boiler holes (see figure).
If the boiler do not have them, insert
the probe at twice the diameter from
the boiler and in central position in the
stack.