Warning – SUUNTO VYTEC DS User Manual

Page 30

Advertising
background image

28

plus

the time needed to reach the surface after the ceiling and safety
stops have been completed.

WARNING!

YOUR ACTUAL ASCENT TIME MAY BE LONGER THAN DISPLAYED
BY THE INSTRUMENT! The ascent time will increase if you:

remain at depth

ascend slower than 10 m/min [33 ft/min] or

make your decompression stop deeper than at the ceiling.

These factors will also increase the amount of air required to reach
the surface.

CEILING, CEILING ZONE, FLOOR AND

DECOMPRESSION RANGE

When in decompression, it is important that you understand the meaning
of ceiling, fl oor, and decompression range (Fig. 3.20.):

The ceiling is the shallowest depth to which you should ascend

when in decompression. At this depth, or below, you must perform
all stops.

The ceiling zone is the optimum decompression stop zone. It is

the zone between the minimum ceiling and 1.8 m [6 ft] below the
minimum ceiling.

The

fl oor is the deepest depth at which the decompression stop time

will not increase. Decompression will start when you pass this depth
during your ascent.

The decompression range is the depth range between the ceiling

and fl oor. Within this range, decompression takes place. However, it
is important to remember that the decompression will be very slow
at, or close to, the fl oor.

The depth of the ceiling and fl oor will depend on your dive profi le. The
ceiling depth will be fairly shallow when you enter the decompression
mode, but if you remain at depth, it will move downward and the ascent
time will increase. Likewise, the fl oor and ceiling may change upwards
while you are decompressing.

When conditions are rough, it may be diffi cult to maintain a constant depth
near the surface. In this case it will be more manageable to maintain an
additional distance below the ceiling, to make sure that the waves do not

Advertising