2 connection procedure – VEGA VEGABAR 17 User Manual

Page 13

Advertising
background image

C

onnect the cable screen on both ends to ground potential.

I

f potential equalisation currents are expected, the connection on the

processing side must be made via a ceramic capacitor (e. g. 1 nF,
1500 V). T

he low frequency potential equalisation currents are thus

suppressed, but the protective effect against high frequency interfer-

ence signals remains.

Warning:
C

onsiderable potential differences exist inside galvanic plants as well

as vessels with cathodic corrosion protection. Very large equalisation
currents can flow through the cable screen when the screen is

grounded on both ends. To avoid this, the cable screen must be
connected to ground potential only on one end (inside the switching
cabinet) in such applications. The cable screen must not be
connected to the internal ground terminal in the sensor and the outer
ground terminal on the housing not to potential equalisation!

Information:
T

he metallic parts of the instrument (antenna, transmitter, concentric

tube, etc.) are conductively connected with the inner and outer ground
terminal on the housing. This connection exists either as a direct
metallic contact or via the shielding of the special connection cable on
instruments with external electronics. You can find specifications on

the potential connections within the instrument in chapter "Technical
data
".

T

ake note of the corresponding installation regulations for Ex

applications.

5

.2 Connection procedure

P

roceed as follows:

1

L

oosen the screw on the rear of the plug connector

2

R

emove the plug connector and seal from VEGABAR 17

3

R

emove the plug insert from the plug housing

Cable screening and
grounding

Select connec-
tion cable for Ex
applications

Connection via angle
plug connector

VEGABAR

17

13

5 C

onnecting to power supply

27636

-

EN

-120531