Maintenance and fault rectification

7

.1 Maintenance

I

f the instrument is used properly, no special maintenance is required

in normal operation.

7

.2 Remove interferences

T

he operator of the system is responsible for taking suitable measures

to rectify faults.

VEGABAR

17

offers maximum reliability. Nevertheless, faults can

occur during operation. These may be caused by the following, e.g.:

l

S

ensor

l

P

rocess

l

V

oltage supply

l

S

ignal processing

T

he first measure to be taken is to check the output signal. In many

cases, the causes can be determined this way and the faults rectified.

S

hould these measures not be successful, please call in urgent cases

the VEGA service hotline under the phone no. +49 1805 858550.

T

he hotline is available to you 7 days a week round-the-clock. Since

we offer this service world-wide, the support is only available in the
E

nglish language. The service is free of charge, only the standard

telephone costs will be charged.

?

N

o 4 … 20 mA signal

l

C

onnection to voltage supply wrong

à Check connection according to chapter "Connection steps"

and if necessary, correct according to chapter "Wiring plan"

l

N

o voltage supply

à Check cables for breaks; repair if necessary

l

O

perating voltage too low or load resistance too high

à Check, adapt if necessary

?

S

teady output signal with pressure change

l

electronics module or measuring cell defective

à Exchange the instrument or send it in for repair

I

n Ex applications, the regulations for the wiring of intrinsically safe

circuits must be observed.

Reaction when malfunc-
tions occur

Failure reasons

Fault rectification