4 mounting, 1 general instructions, 4 m ounting – VEGA VEGABAR 75 4 … 20 mA_HART User Manual

Page 12

Advertising
background image

4 M

ounting

4

.1 General instructions

M

ake sure that the wetted parts of VEGABAR 75, especially

the seal and process fitting, are suitable for the existing

process conditions such as pressure, temperature etc. as well
as the chemical properties of the medium.

Y

ou can find the specifications in chapter "Technical data" in

the "Supplement".

Caution:
A

fter removal of the diaphragm protective cover, the dia-

phragm must not be pressed.

l

T

he connection cable has a capillary for atmospheric

pressure compensation

à Lead the cable end into a dry space or into a suitable

terminal housing.

Information:
VEGA

recommends the breather housing VEGABOX 02 or the

indication/adjustment VEGADIS 12. Both contain terminals
and a ventilation filter for pressure compensation. For

mounting outdoors, a suitable protective cover is available.

H

igher process temperatures often mean also higher ambient

temperatures. Make sure that the upper temperature limits
stated in chapter "Technical data" for the environment of the
electronics housing and connection cable are not exceeded.

Materials, wetted parts

Diaphragm protec-
tion

Connection

Temperature limits

12

VEGABAR

75 - 4 … 20

mA/HART

M

ounting

28433

-EN

-070718

Advertising