6 set up, 1 setup steps without vegadis 12, 2 setup steps with vegadis 12 – VEGA VEGABAR 75 4 … 20 mA_HART User Manual

Page 19: 6 s et up

Advertising
background image

6 S

et up

6

.1 Setup steps without VEGADIS 12

A

fter mounting and electrical connection, VEGABAR 75 is

ready for operation.

à Switch on voltage
T

he electronics now carries out a self-check for approx. 2

seconds. Then VEGABAR 75 delivers a current of 4 … 20 mA
according to the actual level.

6

.2 Setup steps with VEGADIS 12

l

zero - measuring range begin

l

span - measuring range end

l

ti - Integration time

VEGADIS 12

TRANSMITTER

+

4...20mA

+

not used

8

7

6

5

12

11

10

1 2 3

-

-

OPERATE

ti

ZERO

SPAN

TRANSMITTER

1

2

3

Fig. 8: Adjustment elements of VEGADIS 12
1

Rotary switch: choose the requested function

2

[+] key, change value (rising)

3

[-]

key, change value (falling)

l

W

ith the rotary switch the requested function is selected

l

W

ith the [+] and [-] keys, the signal current or the

integration time are adjusted

l

F

inally the rotary switch is set to position "OPERATE"

T

he set values are transmitted to the EEPROM memory and

remain there even in case of voltage loss.

P

roceed as follows for adjustment with VEGADIS 12:

1

O

pen housing cover

2

C

onnect hand multimeter to terminals 10 and 12

3

M

eas. range begin: Set rotary switch to "zero"

Adjustment volume

Adjustment system

Adjustment steps, adjustment

VEGABAR

75 - 4 … 20

mA/HART

19

S

et up

28433

-

EN

-070718