VEGA VEGACAP 82-98 User Manual

Page 5

Advertising
background image

VEGACAP

5

Buildup resistant

(VEGACAP 26, 27, 35 and 98)
The special mechanical construction com-
pensates conductive buildup. Leakage cur-
rents caused by build-up are drained off via
the screen segment.

Even strong condensation or buildup do not
influence the switching condition of VE-
GACAP.

The compensation of buildup is supported
by the patented processing technology
(phase selective admittance processing) in
the oscillator CAP E31 R.

VEGACAP 35 can be shortened locally to the
requested length. Planning and stocking is
thereby facilitated.

Adjustment-free

(VEGACAP 27, 35 and 98)
Set-up is very easy because the switching
point must no longer be adjusted.

Adjustment-free means that changing medi-
ums with different dielectric constant figures
(

e

r

), e.g. water and oil or conductive and non-

conductive mediums, do not influence the
adjustments on VEGACAP and the switching
accuracy.

With vertical installation, the switching point is
only determined by the length of the elec-
trode.

All products with a dielectric constant

³ 1.5

can be detected. With a DK value < 2 a fresh
adjustment must be carried out on VEGACAP
27 and 98.

Product description

With horizontally installed electrodes, the
installation position is also the position of the
switching point.

Note

Check for correct functioning of the sensor.
When filling for the first time, make sure that
VEGACAP responds and switches correctly
so that in case of failure, the filling or empty-
ing process can be manually stopped.