VEGA VEGAWELL 72 4 … 20 mA_HART User Manual

Page 24

Advertising
background image

4

E

mpty the vessel or reduce process pressure

5

S

et a current of 4 mA with the [+] and [-] keys

6

M

eas. range end: Set rotary switch to "span"

7

F

ill the vessel or increase process pressure

8

S

et a current of 20 mA with the [+] and [-] keys

9

O

peration: Set rotary switch to "OPERATE"

10 C

lose housing cover

T

he adjustment data are effective, the output current 4 … 20 mA

corresponds to the actual level.

Information:
T

he corresponding current values must be calculated and set

respectively for adjustment with part fillings or emptyings.

E

xample: For a part emptying of 25 %, a current of 4 mA +

4

mA = 8 mA must be set, for a part filling of 75 %, a current of

4

mA + 12 mA = 16 mA. VEGAWELL 72 then calculates the

values for full and empty.

P

roceed as follows for the adjustment of the integration time

with VEGADIS 12:

1

O

pen housing cover

2

S

et rotary switch to "ti"

3

M

ake sure that the integration time is set to 0 sec by

pressing the [-] key 10 times.

4

F

or every 1 sec. requested integration time, push the [+]

key once.

5

T

he integration time is the time required by the output

current signal to reach 90 % of the actual height after a
sudden level change.

6

S

et rotary switch to "OPERATE"

7

C

lose housing cover

T

he display outputs the current 4 … 20 mA as bar graph and

digital value.

W

ith 4 mA no segment of the bar graph appears, with 20 mA

all segments appear. This assignment is fix.

Y

ou can scale the digital value to any value between -9999 …

+

9999

via the adjustment module.

P

roceed as follows for scaling the indication of VEGADIS 12:

1

O

pen housing cover

Adjustment steps, inte-
gration time

Adjustment steps, scal-
ing

24

VEGAWELL

72 • 4 … 20

mA/HART

6 S

et up

27630

-EN

-080806