6 set up, 1 adjustment of the pressure transmitter, Zero - measuring range begin – VEGA VEGADIS 12 User Manual
Page 16: Span - measuring range end, Ti - integration time 1 2 3
6 Set up
6.1 Adjustment of the pressure transmitter
l
zero - measuring range begin
l
span - measuring range end
l
ti - Integration time
1
2
3
VEGADIS 12
TRANSMITTER
+
4...20mA
+
not used
8
7
6
5
12
11
10
1 2 3
-
-
OPERATE
ti
ZERO
SPAN
TRANSMITTER
Fig. 7: Adjustment elements of VEGADIS 12 without display
1
Rotary switch: choose the requested function
2
[+] key, change value (rising)
3
[-] key, change value (falling)
VEGADIS 12
TRANSMITTER
+
4...20mA
+
DISPLAY
8
7
6
5
12
11
10
1 2 3
-
-
OPERATE
ti
ZERO
SPAN
TRANSMITTER
OPERATE
ZERO
END
POINT
DISPLAY
1
2
4
5
6
3
Fig. 8: Adjustment elements of VEGADIS 12 with display
1
Rotary switch pressure transmitter: Select requested function
2
[+] key, change adjustment value (rising)
3
[-] key, change adjustment value (falling)
4
Rotary switch indication: choose the requested function
5
[+] key, change scaling (rising)
6
[-] key, change scaling (falling)
Adjustment volume
Adjustment elements
16
VEGADIS 12
Set up
20591
-EN
-071128