2 indication scaling – VEGA VEGADIS 12 User Manual

Page 18

Advertising
background image

5 The integration time is the time required by the output

current signal to reach 90 % of the actual height after a

sudden level change.

6 Set rotary switch to "OPERATE"
7 Close the housing cover

6.2 Indication scaling

1

2

3

Fig. 9: Indicating elements of VEGADIS 12

1

Bar graph

2

Tendency indication

3

Digital value

l

four positions as well as signa and decimal point

l

individual scaling between -9999 … +9999

The display outputs the current 4 … 20 mA as bar graph and

digital value.
With 4 mA no segment of the bar graph appears, with 20 mA

all segments appear. This assignment is fix.
You can scale the digital value to any value between -9999 …

+9999 via the adjustment module.

To scale, proceed as follows:
1 Open housing cover
2 Initial value: Set rotary switch to "zero"
3 Set the requested value, e.g. 0 with the [+] and [-] keys
4 Final value: Set the rotary switch to "span"
5 Set the requested value, e.g. 1000 with the [+] and [-] keys
6 Decimal point: Set the rotary switch to "point"
7 With the [+] and [-] keys you can adjust the requested

value, e.g. 8888 (no decimal point)

8 Set rotary switch to "OPERATE"
9 Close the housing cover

Indicating elements

Adjustment steps, scaling

18

VEGADIS 12

Set up

20591

-EN
-071128

Advertising