VEGA VEGAPULS 41 4 … 20 mA; HART compact sensor User Manual

Page 21

Advertising
background image

VEGAPULS 41 – 4 … 20 mA

21

26620-EN-041227

75 %

0 %

100 %

Strong product movements

Strong product movements

Strong turbulence in the vessel, e.g. caused
by powerful stirrers or strong chemical reac-
tions, can seriously interfere with the meas-
urement. A surge or bypass tube (see
illustration) of sufficient size always enables
reliable and problem-free measurement even
if strong turbulence occurs in the vessel,
provided there is no product buildup in the
tube.

Correct

Incorrect

Buildup

Correct

Incorrect

Inflowing material

Correct

Incorrect

Inflowing material

Do not mount the instrument in or above the
filling stream. Ensure that you detect the
product surface and not the inflowing mate-
rial.

Buildup

If the sensor is mounted too close to the
vessel wall, product buildup and other de-
posits on the vessel wall cause false echoes.
Position the sensor at a sufficient distance
from the vessel wall. Please also note chapter
"3.1 General installation instructions“.

Mounting and installation