VEGAPULS 41 – 4 … 20 mA

33

26620-EN-041227

2

2

4 … 20 mA

4

2

2

Measuring system with VEGAPULS 41 on active PLC

• Two-wire technology, power supply from active PLC.
• Output signal 4 … 20 mA (passive).
• Measured value display integrated in the sensor.
• Optional external indicating instrument (can be mounted up to 25 m away from the sensor in

Ex area).

• Adjustment with PC, HART

®

handheld or the adjustment module MINICOM (can be plugged

into the sensor or into the external indication instrument).

HART

®

handheld

VEGA-
CONNECT

Electrical connection

1)

If the resistance of the processing systems
connected to the 4 … 20 mA signal output is less
than 250

Ω, a resistor must be connected to the

connection cable during adjustment to get a loop
resistance of 250

Ω.

The digital adjustment signal would otherwise be
severely damped or short-circuited due to
insufficient resistance of the connected processing
system. Digital communication with the PC would
not be ensured.

1 )

VEGADIS 50

passive

2)

PLC (active)

3)

2)

4 … 20 mA passive means that the sensor
consumes a level-dependent current of
4 … 20 mA. The sensor reacts electrically like a
varying resistor (consumer) to the PLC.

3)

Active means that the PLC powers the passive
sensor as voltage source.