5 common installation mistakes, Parabolic effects on dished or arched vessel tops, Sensor too close to the vessel wall – VEGA VEGAPULS 41 4 … 20 mA; HART compact sensor User Manual

Page 22: Wrong orientation to the product, Socket piece too long

Advertising
background image

22

VEGAPULS 41 – 4 … 20 mA

26620-EN-041227

Unfavourable

Mounting on a vessel with parabolic tank top

Correct

Unfavourable

Parabolic effects on dished or arched
vessel tops

Round or parabolic tank tops act on the ra-
dar signals like a parabolic mirror. If the radar
sensor is placed at the focal point of such a
parabolic tank top, the sensor receives am-
plified false echoes. The optimum mounting
location is generally in the range of half the
vessel radius from the centre.

Sensor too close to the vessel wall

If the radar sensor is mounted too close to
the vessel wall, strong false echoes can be
caused. Buildup, rivets, screws or weld joints
superimpose their echoes onto the product
i.e. useful echo. Please ensure a sufficient
distance from the sensor to the vessel wall.

Direct sensor vertically to the product surface

Correct

Incorrect

Ladder

Ladder

Wrong orientation to the product

Weak measuring signals are generated if the
sensor is not directly pointed at the product
surface. Orient the sensor axis perpendicu-
larly to the product surface to achieve opti-
mum measuring results.

2.5 Common installation mistakes

Socket piece too long

If the sensor is mounted in a socket exten-
sion that is too long, strong false echoes are
generated which interfere with the measure-
ment. Make sure that the horn antenna pro-
trudes out of the socket piece.

Flange antenna: Correct and unfavourable socket
length

Mounting and installation

Correct

Unfavourable

Reference plane

Advertising