VEGA VEGABAR 40 HART User Manual

Page 16

Advertising
background image

16

VEGABAR 40 (HART

®

)

Setup

2 Adjustment of span

(e.g. process pressure or level at maximum)
• Set rotary switch to span.
• By pushing the "+“ and "–“ keys simultane-

ously, the current jumps directly to 20 mA
or set it to 20 mA by pushing the "+“ and "–
“ keys.

Adjustment range of span:
3.3 % … 120 % of the nominal measuring
range (corresponds to turn down 1 : 30)

Note:

- A modification of zero does not influence

the span, i.e. the measuring range final
value is shifted.

- It is also possible to adjust currents for

partial fillings or partial pressures, e.g.
8 mA for 25 % and 16 mA for 75 %. VEGA-
BAR automatically calculates the current
values for 0 % or 100 % (only possible with

3.3 %).

Integration time

An integration time t

i

of 0 … 10 s can be ad-

justed for damping pressure shocks.

Procedure
• Set rotary switch to t

i

.

• By pushing the "–“ key 10 times, make

sure that the integration time is set to 0 s.

• Push the "+“ key once for every 1 s inte-

gration time required.

The integration time is the time required by
the current output signal to reach 90 % of the
actual level after a sudden change of the
process pressure.

Advertising