4 approvals and certificates – VEGA VEGABAR 40 HART User Manual

Page 9

Advertising
background image

VEGABAR 40 (HART

®

)

9

Product description

Operating conditions

Ambient conditions

Ambient temperature

-40°C … +85°C

- with indicating module

-20°C … +70°C

Storage and transport temperature

-40°C … +85°C

Product temperature, dependent on the
seal material of the measuring cell
- Viton

-20°C … +100°C

- EPDM

-40°C … +100°C

- Hifluour

-10°C … +100°C

- Kalrez

0°C … +100°C

1.4 Approvals and certificates

Approvals

- Ex Zone 2
- StEx Zone 10
- Ship approval
- CENELEC EEx ia IIC
- ATEX II 1G EEx ia IIC
- ATEX II 2G EExd ia IIC

If the use of approved instruments is required for certain applications, the respective offi-
cial documents (test reports, test certificates and conformity certificates) must be ob-
served. These are supplied with the respective instrument.

CE conformity

VEGABAR 40 corresponds to the requirements of EMC (89/336/EWG) and NSR
(73/23/EWG). Conformity has been judged acc. to the following standards:
EMC

Emission

EN 50 081 - 1: 1992

Susceptibility

EN 50 082 - 2: 1995

NSR

EN 61 010 - 1: 1993

NAMUR regulations

Full compliance with the NAMUR regulations NE 21 and NE 43.