these vessels. They represent the correlation between the level
percentage and vessel volume. By activating the appropriate curve,
the volume percentage of the vessel is displayed correctly. If the
volume should not be displayed in percent but e.g. in l or kg, a scaling
can be also set in the menu item "Display".

L

inearisation curve

Linear

E

nter the requested parameters via the appropriate keys, save your

settings and jump to the next menu item with the [->] key.

H

igh sockets or vessel installations, such as e. g. struts or agitators as

well as buildup and weld joints on the vessel walls, cause interfering
reflections which can impair the measurement. A false echo storage
detects and marks these false echoes, so that they are no longer taken
into account for the level measurement. A false echo memory should
be created with low level so that all potential interfering reflections can
be detected.

F

alse signal suppression

C

hange now?

P

roceed as follows:

1

M

ove from the measured value display to the main menu by

pushing [OK].

2

S

elect the menu item "Service" with [->] and confirm with [OK].

N

ow the menu item "False signal suppression" is displayed.

3

C

onfirm "False signal suppression - Change now" with [OK] and

select in the below menu "Create new". Enter the actual distance
from the sensor to the product surface. All false signals in this area
are detected by the sensor and saved after confirming with [OK].

Note:
C

heck the distance to the product surface, because if an incorrect (too

large) value is entered, the existing level will be saved as false signal.
T

he filling level would then no longer be detectable in this area.

T

he menu item "Extended setting" offers the possibility to optimise

VEGAPULS

63

for applications in which the level changes very

quickly. To do this, select the function "Quick level change > 1 m/min.".

E

xtended setting

quick level change > 1 m/min.

False signal suppres-
sion

Extended setting/Quick
level change

32

VEGAPULS

63 • 4 … 20

mA/HART - four-wire