VEGA VEGABAR 65 4 … 20 mA_HART User Manual

Page 35

Advertising
background image

5

C

onfirm with [+] and move to max. adjustment with [->].

T

he min. adjustment is finished.

Information:
F

or an adjustment with filling, you simply enter the displayed actual

measured value. If the adjustment ranges are exceeded, the message
"Outside parameter limits" appears. The editing procedure can be
aborted with [ESC] or the displayed limit value can be accepted with
[OK]

.

P

roceed as follows:

1

E

dit the % value in the menu item "Max. adjustment" with [OK].

M

ax. adjustment

+100

.0 %

=

+1000

.0 mbar

0000.0

mbar

Information:
T

he displayed pressure for 100 % corresponds to the nominal

measuring range of the sensor (in the above example 1 bar =
1000

mbar).

2

S

et the requested percentage value with [->] and [OK].

3

E

dit the requested mbar value with [OK].

4

S

et the requested mbar value with [+] and [->].

5

C

onfirm with [OK] and move to the menu overview with [ESC].

T

he max. adjustment is finished.

Information:
F

or an adjustment with filling, you simply enter the displayed actual

measured value. If the adjustment ranges are exceeded, the message
"Outside parameter limits" appears. The editing procedure can be
aborted with [ESC] or the displayed limit value can be accepted with
[OK]

.

Process pressure measurement

S

et up VEGABAR 65 in the following sequence:

1

S

elect application "Process pressure measurement"

2

S

elect the unit of measurement

3

C

arry out position correction

4

C

arrying out zero adjustment

5

C

arrying out span adjustment

I

n the menu item "Adjustment unit" you select the physical unit in which

the adjustment should be carried out, e.g. mbar, bar, psi…

Carrying out max. ad-
justment

Parameter ad-
justment "Proc-
ess pressure
measurement"

VEGABAR

65 • 4 … 20

mA/HART

35

6 S

et up with the indicating and adjustment module PLICSCOM

27531

-

EN

-081209