6 instrument repair – VEGA VEGABAR 65 4 … 20 mA_HART User Manual

Page 52

Advertising
background image

C

onnect the sensor to power supply and provide connection from PC

to the instrument via VEGACONNECT. Start PACTware and provide
connection to the sensor, e.g. via the VEGA project assistant. Close
the parameter window of the sensor, as far as open.

G

o in the PACTware menu bar to "Instrument data", "Additional

functions" and "Update instrument software".

PACT

ware checks now the actual hardware and software version of

the sensor and displays the data. This procedure lasts approx. 60 s.

P

ush the button " Update software" and select the previously

extracted hex file. Then the software update can be started. Further

les are installed automatically. Depending on the sensor, this

procedure lasts approximately 1 h.

8.6 Instrument repair

I

f a repair is necessary, please proceed as follows:

Y

ou can download a return form (23 KB) from our Internet homepage

www.vega.com under: "Downloads - Forms and certificates - Repair
form
".

B

y doing this you help us carry out the repair quickly and without

having to call back for needed information.

l

P

rint and fill out one form per instrument

l

C

lean the instrument and pack it damage-proof

l

A

ttach the completed form and, if need be, also a safety data

sheet outside on the packaging

l

P

lease ask the agency serving you for the address of your return

shipment. You can find the respective agency on our website
www.vega.com under: "Company - VEGA worldwide"

Prepare update

Load software into sen-
sor

52

VEGABAR

65 • 4 … 20

mA/HART

8 M

aintenance and fault rectification

27531

-EN

-081209