2 mounting, 1 installation instructions – VEGA VEGAFLEX 54K User Manual

Page 14

Advertising
background image

14

VEGAFLEX 54K

Moisture

Mounting

Lateral load

Pressure

In case of gauge or low pressure in the ves-
sel, the mounting boss must be sealed on the
thread. Make sure that the seal ring is resist-
ant to the medium.

2 Mounting

2.1 Installation instructions

Lateral load

Make sure that the cable is not subjected to
strong lateral forces. Mount VEGAFLEX at a
location where no interference caused by,
e.g., stirrers, filling inlets etc. can occur.

Cable entries

When mounting outdoors, on cooled vessels
or in humid areas where cleaning is done,
e.g. with steam or high pressure, the seal of
the electrical cable entry is very important.

Use electrical cable with a round cross-sec-
tion and tighten the cable entry firmly. The
cable entry is suitable for cable diameters of
5 mm to 9 mm.

Moisture from outside

To avoid moisture ingress, the connection
cable leading to the housing should be
looped downward (directly in front of the
cable entry), so that rain and condensation
water can drain off. This mainly applies to
outdoor mounting, in areas where moisture is
expected (e.g. by cleaning processes) or to
cooled or heated vessels.

Advertising