5 diagnosis, 1 simulation, 2 failure rectification – VEGA VEGAFLEX 54K User Manual

Page 32

Advertising
background image

32

VEGAFLEX 54K

5 Diagnosis

5.1 Simulation

To simulate a certain filling, you can call up the function "Simulation" on the adjustment module
MINICOM, in the software program VVO or in the HART

®

handheld. This function simulates a

certain current value. Please keep in mind that connected devices, such as e.g. a PLC, react
according to their settings and will probably activate alarms or system functions.

5.2 Failure rectification

Error

Corrective measure

E 013

Sensor does not find a

- Message is displayed during the warm-up

level echo

phase.

- If the message remains, the DK value of the

medium might be too low.

Check the useful level and noise level.
See "4.2 Adjustment with adjustment module
MINICOM; 6. Useful level and noise level".
If the message still remains, carry out a new
adjustment.

E 017

Adjustment span too small

Carry out the adjustment again. Make sure that
the difference between min. and max. adjust-
ment is at least 10 mm.

E 036

Software update incorrect

Return the instrument for repair.

E 040

Hardware failure/

Check all connection cables.

Electronics defective

Contact our service department.

Diagnosis

Advertising