VEGA VEGAFLEX 54K User Manual

Page 24

Advertising
background image

24

VEGAFLEX 54K

Setup

2. Conditioning

Under the menu item "

Conditioning" you

choose the distance at 0 % and at 100 %
filling. Then you enter the physical quantity
and the unit as well as the decimal point.
• Enter in the menu window "

0 % corre-

spond" the value of the 0 % filling. This will
be e.g. "80" for 80 liters.

• Confirm with "

OK".

• With the arrow key you switch to the 100 %

menu. Enter here the value of your param-
eter corresponding to a 100 % filling. E.g.
"1200" for 1200 liters.

• Confirm with "

OK".

• If necessary, choose a decimal point. Note

that max. 4 digits can be shown.

• In the menu "

prop. to", you choose the

parameter (mass, volume, distance…),

• In the menu "

Unit", you choose the physical

unit (kg, l, ft

3

, gal, m

3

…).

• With the "ESC" key, you go back to the next

higher menu level. With the arrow key, you
choose the next menu item.

• In the menu

"Lin. curve", you can choose

between three standard linearisation
curves.
A linear correlation between percentage
value of the product distance and the per-
centage value of the filling volume has
been preset.
You can choose between linear, spherical
and cylindrical tank. Entering a user-pro-
grammable curve is only possible with the
PC and the adjustment program VVO.

• In the menu item

"Integration time", you can

set a delay period for the signal output.

3. Outputs

Under the menu "

Outputs", you determine

e.g. if the current output should be inverted,
or which parameter should be indicated on
the sensor display.

4. Operating range

Without special adjustment, the operating
range corresponds to the measuring range.
The measuring range was already adjusted
with the min./max. adjustment. It is generally
better to choose a slightly wider span for
operating range (approx. 5 %) than for the
measuring range (span).

Example:
Min./Max. adjustment: 0.300 … 5.850 m; set
operating range to approx. 0.250 … actual
cable length.

5. Meas. conditions

With these functions, you can enter the ambi-
ent conditions in the vessel (see menu sche-
matic).

Advertising