2 survey – VEGA VEGAPULS 51K…54K Profibus PA User Manual

Page 12

Advertising
background image

12

VEGAPULS 51P … 54P

24890-EN-041227

2.2 Survey

Short overview of sensor features

• Application preferably for liquids in storage tanks or vessels.
• Measuring range 0 … 20 m.
• Ex approved in Zone 1 (IEC) or Zone 1 (ATEX) classification mark

EEx ia [ia] IIC T6.

• Integrated display of measured values.

Overview

VEGAPULS

51P

52P

53P

54P

Signal output
– digital meas. signal (PA)

Voltage supply
– PA two-wire technology (voltage

supply and signal output
via one two-wire cable)

Process fitting
– G1

1

/

2

A; 1

1

/

2

“ NPT

– DN 50; ANSI 2“

– DN 80; ANSI 3“

– DN 100; ANSI 4“

– DN 150; ANSI 6“

Adjustment with
– PC with adjustment software

– adjustment module in the sensor

– adjustment module in external

indicating instrument

- SIMATIC PDM

- PACTware™ (VVO runs as

subprogram)

Antenna material
– PP/PVDF

– PPS/StSt

– PTFE/PVDF

– PTFE/StSt

– PTFE

– StSt/PTFE

– Hastelloy C22/PTFE

Types and versions

The antenna is available with or without horn.
Versions with horn are characterised by very
good antenna gain. High measurement reli-
ability can be achieved even in case of prod-
ucts with very poor reflective properties.

The measuring tube acts as a conductor for
radar signals. The running period of the ra-
dar signals changes in the tube and de-
pends on the tube diameter. The tube inner
diameter must be programmed into the sen-
sor so that it can take the altered running time
into account and deliver precise level signals.